Honeywell ZyAIR G-3000 2*02, 2*17, 2*18, 2*19, 2*20, 2*21, VISTA-40Installation and Setup Guide

Page 58
2*02

VISTA-40 Installation and Setup Guide

FIELD

TITLE and DATA ENTRIES

EXPLANATION

 

 

 

 

2*02

 

Daylight Saving Time Start/End

 

 

Weekend

 

 

 

 

 

0

= disable

 

 

1

= enable

 

 

 

 

 

2*17

Number of Codes per Partition

Enter 01-69

 

 

2*18

 

Enable GOTO for this Partition

 

 

(partition-specific)

 

 

 

 

 

0

= disable

 

 

1

= enable

 

 

 

 

 

 

 

Use Partition Descriptor

 

2*19

 

 

0

= disable

 

 

 

 

1

= enable

 

 

 

 

 

 

 

Enable J7 Triggers for Partition

 

2*20

 

 

 

(partition-specific)

 

 

 

 

 

0

= disable

 

 

1

= enable

 

 

 

 

 

 

 

Supervision Pulses for LRR

 

2*21

 

 

0

= disable

 

 

 

 

1

= enable

 

 

 

 

 

Enter the start and end weekends for daylight saving time as follows: 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next to last; 7=third from last. Standard setting for U.S. is 1,5.

This field has two 2-digit entries. Enter the number user codes for each partition. The total number of user codes cannot exceed 70 for the system. Enter 01 for an unused partition.

NOTE: The installer code is automatically assigned to each partition regardless of whether that partition has been enabled.

If enabled, this partition can be accessed from another partition’s keypad using the GOTO command.

If enabled, the normal keypad display will include a partition number and four-digit descriptor.

If enabled, the J7 triggers function for this partition.

There are three entries in this field as follows: Fire, Burglary/Audible Panic, Silent Panic/Duress.

If enabled, causes the control to send periodic short pulses on the J7 radio triggers to the LRR. The LRR uses these pulses to determine that its connection to the control is still intact.

Must be 1 for UL installations.

5-12

Image 58
Contents QVWDOODWLRQDQG6HWXS*XLGH $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP N7001V5 5/04 Rev APage Table of Contents Index List of Figures Conventions Used in This Manual PRODUCT MODEL NUMBERSS E C T I O N FeaturesGeneral Description About the VISTA-40Additional Features VISTA-40Installation and Setup GuideEvent Log Theory of Partitioning Setting-Upa Partitioned SystemPartitioning S E C T I O NVISTA-40Installation and Setup Guide Mounting the Control Cabinet Installing the ControlInstalling the Cabinet Lock Grade A Mercantile Premises Listing GuidelinesVISTA-40Installation and Setup Guide Installing the Control’s Circuit BoardStep Action Wire Run Length/Gauge Table Installing the KeypadsSection 3 - Installing the Control Wire GaugeAlarm Output Supervision Installing External SoundersVISTA-40Installation and Setup Guide Wiring the Alarm OutputSupervising the Alarm Output Telephone Line ConnectionsSection 3 - Installing the Control Using a Siren DriverTERMINALS VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones ON CONTROLCompatible 2-WireSmoke Detectors Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Using 4-WireSmoke Detectors on ZonesInstalling the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Smoke Detectors Compatible with the 333PRMFOUR-WIREDETECTOR CIRCUIT Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT CONTROL PANELUsing 2-WireLatching Glassbreaks on Zone Installing RPM DevicesVISTA-40Installation and Setup Guide 3-10Step Action Section 3 - Installing the Control3-11 Figure 3-16 Polling Loop Connections to the3-12 VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender Polling Loop SupervisionRF System Installation Advisories Wireless Zone ExpansionSection 3 - Installing the Control Installation and Setup of the 5881 RF ReceiversStep Action VISTA-40Installation and Setup Guide3-14 StepThe 5800TM must not be installed within Section 3 - Installing the ControlInstalling the 5800TM Module 5800 Series Transmitter SetupTransmitter Battery Life Installing Relay DevicesVISTA-40Installation and Setup Guide Installing the 4204 Relay ModulesInstalling X10 Devices Installing the Ground Start ModuleSection 3 - Installing the Control The wire that reads + 50VDC is the RING sideKeyswitch Tamper Operation Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Wiring for the Remote KeyswitchLong Range Radio Connected to the J7 Triggers Installing a 4100SMRemote Keypad Sounder Section 3 - Installing the ControlConnecting the 4100SM to a Serial Printer Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide UL installationsStep Action Section 3 - Installing the Control3-21 Step ActionVISTA-40Installation and Setup Guide Installing the Audio Alarm Verification Module3-22 3-23 Connecting the TransformerSection 3 - Installing the Control UVCM AND UVST SUMMARY OF CONNECTIONS3-24 VISTA-40Installation and Setup GuidePower Limiting Outputs OutputSection 3 - Installing the Control Determining the Control’s Power Supply LoadPanel Earth Ground Connections AC Power Outlet Ground Available fromTable 3 Alarm Output Current Load Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide AlarmRecommended Battery Section 3 - Installing the ControlTable 6 Battery Selection Table 3-27VISTA-40Installation and Setup Guide 3-28Entering and Exiting Programming Mode ProgrammingProgram Modes Data Field Programming ModeEntry Errors #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide 1Enter Program Mode Installer Code +MAIN MENU VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands OPTIONSZone Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Communication DefaultsType 05 Trouble by Day/Alarm by Night Zone Response Type DefinitionsCommunication Defaults for Zones Section 4 - ProgrammingType 06 24-HourSilent Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 07 24-HourAudible AlarmSection 4 - Programming Programming for Access ControlProgramming for 4100SM StepVISTA-40Installation and Setup Guide Programming Data Fields Data Field DescriptionsAbout Data Field Programming Installer CodeKeyswitch Assignment VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Prevent Fire TimeoutPABX Access Code 24 25 26Power-Upin Previous State Section 5 - Data Field DescriptionsDownload Command Enables 38 39VISTA-40Installation and Setup Guide Enable Open/Close report for KeyswitchFIELD 45 46 47 48 49Section 5 - Data Field Descriptions TITLE and DATA ENTRIESAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesNon-AlarmReport Codes Second Digit 82 83 84VISTA-40Installation and Setup Guide Restore Report Timing1*33 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*341*38 1*361*37 1*391*57 1*491*53 1*582*18 2*022*17 2*19Remote Downloading is not a UL Listed feature Downloading PrimerGeneral Information Access SecurityOn-LineControl Functions Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide Stage What HappensTelco Handoff Direct-WireDownloadingSection 24 - Downloading Primer VISTA-40Installation and Setup Guide S E C T I O N Setting the Real-TimeClockSetting the Time and Date General InformationVISTA-40Installation and Setup Guide Level 0 Installer User 1 Code User Access CodesUser Codes & Levels of Authority S E C T I O NEXAMPLE OF MULTIPLE PARTITION ACCESS Multiple Partition AccessVISTA-40Installation and Setup Guide Level 6 Duress CodesSection 9 - User Access Codes Adding a Master, Manager, or Operator CodePROMPTEXPLANATION Deleting a Master, Manager, or Operator Code Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Exiting the User Edit ModeDialer Test Testing the SystemBattery Test Burglary Walk-TestCode + 5 TESTStep Action 1Enter Installer Code + Testing Wireless TransmittersVISTA-40Installation and Setup Guide Transmitter ID Sniffer ModeSection 10 - Testing The System To the InstallerTrouble Conditions Power FailureTechnical Support VISTA-40Installation and Setup GuideContacting Technical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemRegulatory Agency Statements UL Installation RequirementsUL365 Police Station Connected Burglar Alarm A P P E N D I X AFor Grade A Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade AA ServiceAppendix A - Regulatory Agency Statements IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSFCC PART 68 NOTICE CANADIAN EMISSIONS STATEMENTS VISTA-40Installation and Setup GuideAVIS User Code Commands Programming Commands Summary of System CommandsA P P E N D I X B Event Logging CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide TABLE OF CONTACT ID EVENT CODES Contact ID Event CodesA P P E N D I X D CodeVISTA-40Installation and Setup Guide Index Index-1VISTA-40Installation and Setup Guide Index-2Index Index-3VISTA-40Installation and Setup Guide Index-4THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page ¬19+l 165 Eileen Way, Syosset, New YorkN7001V5 5/04 Rev A