Honeywell ZyAIR G-3000 #93 Menu Mode Programming, VISTA-40Installation and Setup Guide, entry

Page 40
Entry Errors

VISTA-40 Installation and Setup Guide

Entry Errors

If an address is improperly entered, the keypad displays “FC.”

If a program entry is improperly entered (for example, a larger number than is permitted), the keypad display will go blank.

In either of the above cases, simply re-enter [] + the correct field number and then enter the correct data.

Programming System-Wide Data Fields

Values for some programming fields are system-wide (global), and some can be different for each partition (partition-specific).

The partition-specific programming fields are automatically skipped when programming the global fields. If the system has only 1 partition, the partition-specific fields are not automatically skipped.

To program system-wide data fields, perform the following steps:

Step Action

1Enter Program Mode: Installer Code + 8 0 0. The following display appears:

Program Mode

Fill # View – 00

2If the control has not been programmed before, enter 97 to load factory defaults.

3Press [] and enter the first field number to be programmed (for example, 00, Installers Code). Make the desired entry. When the field is complete, the keypad beeps three times and advances to the next field. If you do not want to change the next field, press [] and enter the next field number to be programmed.

 

 

 

First Page of fields

 

 

 

 

 

 

 

 

 

 

 

(00 - 90)

 

 

 

To change to the next page of fields, press 94.

 

To return to the previous page of fields, press

 

99.

 

 

4

Press 99 or 98 to exit Program Mode.

NOTE: If the number of digits that you enter in a data field is fewer than the maximum permitted (for example, a phone number), the keypad displays the last entry and waits. To proceed, enter [] + the next data field you wish to program.

Programming Partition-Specific Data Fields

To program partition-specific data fields once in Program Mode, do the following:

Step Action

1Enter Program Mode: Installer Code + 8 0 0.

2Press 91, which will prompt you for the partition number desired.

3Enter a partition-specific field number (e.g., 09) to begin programming.

When the first field’s entry is completed, the next partition-specific field is automatically displayed. When all partition-specific fields are programmed, the system returns to the global programming fields (page 1 fields).

4Repeat this procedure for the other partition.

NOTE: To return to the global program fields before finishing all fields, enter any global field number.

Programming Partition-Specific Fields
Press 91 to select a partition.

p

Enter the partition to be programmed.

p

Enter a partition-specific field number and make
entry.

p

Enter any global field number to return to the global

fields at any time.

#93 Menu Mode Programming

The #93 Menu Mode is an interactive mode through which much of the system’s programming is done. In this mode, there are “question and answer” prompts that can be accessed once Data Field Program Mode has been entered. These prompts require a 2-line alpha keypad (6139/6160).

After programming all system-related programming fields in the usual way, press #93 while still in programming mode to display the first choice of the menu-driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.

4-2

Image 40
Contents $0&29,67$ 3DUWLWLRQHG6HFXULW\6\VWHPQVWDOODWLRQDQG6HWXS*XLGH N7001V5 5/04 Rev APage Table of Contents Index List of Figures Conventions Used in This Manual PRODUCT MODEL NUMBERSFeatures General DescriptionS E C T I O N About the VISTA-40Additional Features VISTA-40Installation and Setup GuideEvent Log Setting-Upa Partitioned System PartitioningTheory of Partitioning S E C T I O NVISTA-40Installation and Setup Guide Installing the Control Installing the Cabinet LockMounting the Control Cabinet Grade A Mercantile Premises Listing GuidelinesVISTA-40Installation and Setup Guide Installing the Control’s Circuit BoardStep Action Installing the Keypads Section 3 - Installing the ControlWire Run Length/Gauge Table Wire GaugeInstalling External Sounders VISTA-40Installation and Setup GuideAlarm Output Supervision Wiring the Alarm OutputTelephone Line Connections Section 3 - Installing the ControlSupervising the Alarm Output Using a Siren DriverVISTA-40Installation and Setup Guide Figure 3-9 Wiring Connections for ZonesTERMINALS ON CONTROLSection 3 - Installing the Control Using 2-WireSmoke Detectors on ZoneCompatible 2-WireSmoke Detectors Using 4-WireSmoke Detectors on ZonesVISTA-40InstallationTOand Setup Guide Using Smoke Power Reversal ModuleInstalling the 333PRM Smoke Detectors Compatible with the 333PRMSection 3 - Installing the Control FOUR-WIREDETECTOR CIRCUITFOUR-WIREDETECTOR CIRCUIT CONTROL PANELInstalling RPM Devices VISTA-40Installation and Setup GuideUsing 2-WireLatching Glassbreaks on Zone 3-10Section 3 - Installing the Control 3-11Step Action Figure 3-16 Polling Loop Connections to theVISTA-40Installation and Setup Guide Using the 4297 Polling Loop Extender3-12 Polling Loop SupervisionWireless Zone Expansion Section 3 - Installing the ControlRF System Installation Advisories Installation and Setup of the 5881 RF ReceiversVISTA-40Installation and Setup Guide 3-14Step Action StepSection 3 - Installing the Control Installing the 5800TM ModuleThe 5800TM must not be installed within 5800 Series Transmitter SetupInstalling Relay Devices VISTA-40Installation and Setup GuideTransmitter Battery Life Installing the 4204 Relay ModulesInstalling the Ground Start Module Section 3 - Installing the ControlInstalling X10 Devices The wire that reads + 50VDC is the RING sideInstalling a Remote Keyswitch VISTA-40Installation and Setup GuideKeyswitch Tamper Operation Wiring for the Remote KeyswitchInstalling a 4100SM Remote Keypad SounderLong Range Radio Connected to the J7 Triggers Section 3 - Installing the ControlInstalling the 4285/4286 VIP Module VISTA-40Installation and Setup GuideConnecting the 4100SM to a Serial Printer UL installationsSection 3 - Installing the Control 3-21Step Action Step ActionVISTA-40Installation and Setup Guide Installing the Audio Alarm Verification Module3-22 Connecting the Transformer Section 3 - Installing the Control3-23 UVCM AND UVST SUMMARY OF CONNECTIONSVISTA-40Installation and Setup Guide Power Limiting Outputs3-24 OutputDetermining the Control’s Power Supply Load Panel Earth Ground ConnectionsSection 3 - Installing the Control AC Power Outlet Ground Available fromDetermining the Size of the Standby Battery VISTA-40Installation and Setup GuideTable 3 Alarm Output Current Load AlarmSection 3 - Installing the Control Table 6 Battery Selection TableRecommended Battery 3-27VISTA-40Installation and Setup Guide 3-28Programming Program ModesEntering and Exiting Programming Mode Data Field Programming Mode#93 Menu Mode Programming VISTA-40Installation and Setup GuideEntry Errors 1Enter Program Mode Installer Code +VISTA-40Installation and Setup Guide #93 Menu Mode Programming CommandsMAIN MENU OPTIONSZone Number Designations VISTA-40Installation and Setup GuideZone Defaults Communication DefaultsZone Response Type Definitions Communication Defaults for ZonesType 05 Trouble by Day/Alarm by Night Section 4 - ProgrammingZone Input Type Definitions VISTA-40Installation and Setup GuideType 06 24-HourSilent Alarm Type 07 24-HourAudible AlarmProgramming for Access Control Programming for 4100SMSection 4 - Programming StepVISTA-40Installation and Setup Guide Data Field Descriptions About Data Field ProgrammingProgramming Data Fields Installer CodeVISTA-40Installation and Setup Guide Alarm Sounder Duration partition-specificKeyswitch Assignment Prevent Fire Timeout24 25 26 Power-Upin Previous StatePABX Access Code Section 5 - Data Field Descriptions38 39 VISTA-40Installation and Setup GuideDownload Command Enables Enable Open/Close report for Keyswitch45 46 47 48 49 Section 5 - Data Field DescriptionsFIELD TITLE and DATA ENTRIES59 60 61 62 VISTA-40Installation and Setup GuideAlarm Code for Zones Alarm Code for Zones74 75 76 77 Supervisory and Restore CodesAlarm Code for Zones Alarm Code for Zones82 83 84 VISTA-40Installation and Setup GuideNon-AlarmReport Codes Second Digit Restore Report Timing1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*30 1*311*33 1*341*36 1*371*38 1*391*49 1*531*57 1*582*02 2*172*18 2*19Downloading Primer General InformationRemote Downloading is not a UL Listed feature Access SecurityGetting On-Linewith a Control Panel VISTA-40Installation and Setup GuideOn-LineControl Functions Stage What HappensTelco Handoff Direct-WireDownloadingSection 24 - Downloading Primer VISTA-40Installation and Setup Guide Setting the Real-TimeClock Setting the Time and DateS E C T I O N General InformationVISTA-40Installation and Setup Guide User Access Codes User Codes & Levels of AuthorityLevel 0 Installer User 1 Code S E C T I O NMultiple Partition Access VISTA-40Installation and Setup GuideEXAMPLE OF MULTIPLE PARTITION ACCESS Level 6 Duress CodesSection 9 - User Access Codes Adding a Master, Manager, or Operator CodePROMPTEXPLANATION Changing a Master, Manager, or Operator Code Adding an RF Key to an Existing UserDeleting a Master, Manager, or Operator Code Exiting the User Edit ModeTesting the System Battery TestDialer Test Burglary Walk-TestCode + 5 TESTTesting Wireless Transmitters VISTA-40Installation and Setup GuideStep Action 1Enter Installer Code + Transmitter ID Sniffer ModeTo the Installer Trouble ConditionsSection 10 - Testing The System Power FailureVISTA-40Installation and Setup Guide Contacting Technical SupportTechnical Support ATLIS-FAXFAXBACK Automated Fax Retrieval SystemUL Installation Requirements UL365 Police Station Connected Burglar AlarmRegulatory Agency Statements A P P E N D I X AUL611/UL1610 Central Station Burglary Alarm VISTA-40Installation and Setup GuideFor Grade A Service For Grade AA ServiceAppendix A - Regulatory Agency Statements IN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMSFCC PART 68 NOTICE CANADIAN EMISSIONS STATEMENTS VISTA-40Installation and Setup GuideAVIS Summary of System Commands A P P E N D I X BUser Code Commands Programming Commands Event Logging CommandsVISTA-40Installation and Setup Guide Specifications A P P E N D I X CInterface Wiring Interface WiringVISTA-40Installation and Setup Guide Contact ID Event Codes A P P E N D I X DTABLE OF CONTACT ID EVENT CODES CodeVISTA-40Installation and Setup Guide Index Index-1VISTA-40Installation and Setup Guide Index-2Index Index-3VISTA-40Installation and Setup Guide Index-4THE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page ¬19+l 165 Eileen Way, Syosset, New YorkN7001V5 5/04 Rev A