Programming

S E C T I O N 4

Programming

• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •

Program Modes

There are two programming modes for the VISTA-40. These are the Data Field Program Mode and the #93 Menu Mode. The Data Field Program Mode is where many system options are programmed. The #93 Menu Mode is an interactive mode that requires a 2-line alpha keypad (6139/6160).

The factory-loaded defaults (97) enable keypad addresses 00-03 only. A keypad set to one of these addresses must be used to program the system initially.

Local keypad programming can be disabled through Compass downloading software. If this is done, Program mode can only be accessed via the downloading software.

Entering and Exiting Programming Mode

Enter Programming mode using either method a or b:

a.Press both the [] and [#] keys at the same time within 30 seconds after power is applied to the control.

b.Enter the Installer Code + [8] + [0] + [0] keys. The factory installer code can be changed once in the Program mode (field 00).

NOTE: The default for the Installer Code is 4140.

Exit the Programming mode by either method a or b:

a.Press [] + [9] + [8]. Exiting by this method prevents the installer code from being used to re- enter Programming mode. Only method “a” can be used to re-enter Programming mode.

b.Press [] + [9] + [9]. Exiting by this method permits the installer code to be being used to re- enter Programming mode.

Data Field Programming Mode

In the Data Field Program Mode you may access any field simply by entering either [] or [#] + the field number:

To write or change information in a field press [] + the field number (03).

To read the information in a field press [#] + the field number (#03).

When the entries for a field are completed, the keypad beeps three times and advances to the next field.

Summary of Data Field Programming Commands

91 Select partition for programming partition-specific fields

92 Display the software revision level of the control panel

93 Enter Menu mode programming

94 Go to next page of fields

99 Go back to previous page of fields or exit Programming Mode with no installer code lockout

98 Exit Programming Mode with Installer Code lockout

Moving Between Programming Levels

The data fields are grouped into three levels (referred to as “pages”). The first page is accessed as soon as Programming Mode is entered.

The second and third pages of data fields are indicated at the keypad by a 1 and 2, respectively, in front of the 2-digit field address. “ALT PROGRAM MODE” is displayed along with a “100” or “200,” indicating which page of program fields is accessed.

To access the next level of programming fields, perform the following steps:

Step Action

1Press 94.

2Press [7] + [XX], where XX = the last two digits of the program field, and make the desired entry.

NOTES:

Press 94 to move to 2nd page, (fields 101 - 176); press 99 to move back to 1st page.

Press 94 to move to 3rd page (fields 200 - 221); press 99 to move back to 2nd page

4-1

Image 39
Contents N7001V5 5/04 Rev A $0&29,67$3DUWLWLRQHG6HFXULW\6\VWHP QVWDOODWLRQDQG6HWXS*XLGHPage Table of Contents Index List of Figures PRODUCT MODEL NUMBERS Conventions Used in This ManualAbout the VISTA-40 FeaturesGeneral Description S E C T I O NVISTA-40Installation and Setup Guide Additional FeaturesEvent Log S E C T I O N Setting-Upa Partitioned SystemPartitioning Theory of PartitioningVISTA-40Installation and Setup Guide Grade A Mercantile Premises Listing Guidelines Installing the ControlInstalling the Cabinet Lock Mounting the Control CabinetInstalling the Control’s Circuit Board VISTA-40Installation and Setup GuideStep Action Wire Gauge Installing the KeypadsSection 3 - Installing the Control Wire Run Length/Gauge TableWiring the Alarm Output Installing External SoundersVISTA-40Installation and Setup Guide Alarm Output SupervisionUsing a Siren Driver Telephone Line ConnectionsSection 3 - Installing the Control Supervising the Alarm OutputON CONTROL VISTA-40Installation and Setup GuideFigure 3-9 Wiring Connections for Zones TERMINALSUsing 4-WireSmoke Detectors on Zones Section 3 - Installing the ControlUsing 2-WireSmoke Detectors on Zone Compatible 2-WireSmoke DetectorsSmoke Detectors Compatible with the 333PRM VISTA-40InstallationTOand Setup GuideUsing Smoke Power Reversal Module Installing the 333PRMCONTROL PANEL Section 3 - Installing the ControlFOUR-WIREDETECTOR CIRCUIT FOUR-WIREDETECTOR CIRCUIT3-10 Installing RPM DevicesVISTA-40Installation and Setup Guide Using 2-WireLatching Glassbreaks on ZoneFigure 3-16 Polling Loop Connections to the Section 3 - Installing the Control3-11 Step ActionPolling Loop Supervision VISTA-40Installation and Setup GuideUsing the 4297 Polling Loop Extender 3-12Installation and Setup of the 5881 RF Receivers Wireless Zone ExpansionSection 3 - Installing the Control RF System Installation AdvisoriesStep VISTA-40Installation and Setup Guide3-14 Step Action5800 Series Transmitter Setup Section 3 - Installing the ControlInstalling the 5800TM Module The 5800TM must not be installed withinInstalling the 4204 Relay Modules Installing Relay DevicesVISTA-40Installation and Setup Guide Transmitter Battery LifeThe wire that reads + 50VDC is the RING side Installing the Ground Start ModuleSection 3 - Installing the Control Installing X10 DevicesWiring for the Remote Keyswitch Installing a Remote KeyswitchVISTA-40Installation and Setup Guide Keyswitch Tamper OperationSection 3 - Installing the Control Installing a 4100SMRemote Keypad Sounder Long Range Radio Connected to the J7 TriggersUL installations Installing the 4285/4286 VIP ModuleVISTA-40Installation and Setup Guide Connecting the 4100SM to a Serial PrinterStep Action Section 3 - Installing the Control3-21 Step ActionInstalling the Audio Alarm Verification Module VISTA-40Installation and Setup Guide3-22 UVCM AND UVST SUMMARY OF CONNECTIONS Connecting the TransformerSection 3 - Installing the Control 3-23Output VISTA-40Installation and Setup GuidePower Limiting Outputs 3-24AC Power Outlet Ground Available from Determining the Control’s Power Supply LoadPanel Earth Ground Connections Section 3 - Installing the ControlAlarm Determining the Size of the Standby BatteryVISTA-40Installation and Setup Guide Table 3 Alarm Output Current Load3-27 Section 3 - Installing the ControlTable 6 Battery Selection Table Recommended Battery3-28 VISTA-40Installation and Setup GuideData Field Programming Mode ProgrammingProgram Modes Entering and Exiting Programming Mode1Enter Program Mode Installer Code + #93 Menu Mode ProgrammingVISTA-40Installation and Setup Guide Entry ErrorsOPTIONS VISTA-40Installation and Setup Guide#93 Menu Mode Programming Commands MAIN MENUCommunication Defaults Zone Number DesignationsVISTA-40Installation and Setup Guide Zone DefaultsSection 4 - Programming Zone Response Type DefinitionsCommunication Defaults for Zones Type 05 Trouble by Day/Alarm by NightType 07 24-HourAudible Alarm Zone Input Type DefinitionsVISTA-40Installation and Setup Guide Type 06 24-HourSilent AlarmStep Programming for Access ControlProgramming for 4100SM Section 4 - ProgrammingVISTA-40Installation and Setup Guide Installer Code Data Field DescriptionsAbout Data Field Programming Programming Data FieldsPrevent Fire Timeout VISTA-40Installation and Setup GuideAlarm Sounder Duration partition-specific Keyswitch AssignmentSection 5 - Data Field Descriptions 24 25 26Power-Upin Previous State PABX Access CodeEnable Open/Close report for Keyswitch 38 39VISTA-40Installation and Setup Guide Download Command EnablesTITLE and DATA ENTRIES 45 46 47 48 49Section 5 - Data Field Descriptions FIELDAlarm Code for Zones 59 60 61 62VISTA-40Installation and Setup Guide Alarm Code for ZonesAlarm Code for Zones 74 75 76 77Supervisory and Restore Codes Alarm Code for ZonesRestore Report Timing 82 83 84VISTA-40Installation and Setup Guide Non-AlarmReport Codes Second Digit1*34 1*01 1*02 1*03 1*04 1*05 1*09 1*28 1*29 1*301*31 1*331*39 1*361*37 1*381*58 1*491*53 1*572*19 2*022*17 2*18Access Security Downloading PrimerGeneral Information Remote Downloading is not a UL Listed featureStage What Happens Getting On-Linewith a Control PanelVISTA-40Installation and Setup Guide On-LineControl FunctionsDirect-WireDownloading Telco HandoffSection 24 - Downloading Primer VISTA-40Installation and Setup Guide General Information Setting the Real-TimeClockSetting the Time and Date S E C T I O NVISTA-40Installation and Setup Guide S E C T I O N User Access CodesUser Codes & Levels of Authority Level 0 Installer User 1 CodeLevel 6 Duress Codes Multiple Partition AccessVISTA-40Installation and Setup Guide EXAMPLE OF MULTIPLE PARTITION ACCESSAdding a Master, Manager, or Operator Code Section 9 - User Access CodesPROMPTEXPLANATION Exiting the User Edit Mode Changing a Master, Manager, or Operator CodeAdding an RF Key to an Existing User Deleting a Master, Manager, or Operator CodeBurglary Walk-TestCode + 5 TEST Testing the SystemBattery Test Dialer TestTransmitter ID Sniffer Mode Testing Wireless TransmittersVISTA-40Installation and Setup Guide Step Action 1Enter Installer Code +Power Failure To the InstallerTrouble Conditions Section 10 - Testing The SystemATLIS-FAXFAXBACK Automated Fax Retrieval System VISTA-40Installation and Setup GuideContacting Technical Support Technical SupportA P P E N D I X A UL Installation RequirementsUL365 Police Station Connected Burglar Alarm Regulatory Agency StatementsFor Grade AA Service UL611/UL1610 Central Station Burglary AlarmVISTA-40Installation and Setup Guide For Grade A ServiceIN THE EVENT OF TELEPHONE OPERATIONAL PROBLEMS Appendix A - Regulatory Agency StatementsFCC PART 68 NOTICE VISTA-40Installation and Setup Guide CANADIAN EMISSIONS STATEMENTSAVIS Event Logging Commands Summary of System CommandsA P P E N D I X B User Code Commands Programming CommandsVISTA-40Installation and Setup Guide Interface Wiring SpecificationsA P P E N D I X C Interface WiringVISTA-40Installation and Setup Guide Code Contact ID Event CodesA P P E N D I X D TABLE OF CONTACT ID EVENT CODESVISTA-40Installation and Setup Guide Index-1 IndexIndex-2 VISTA-40Installation and Setup GuideIndex-3 IndexIndex-4 VISTA-40Installation and Setup GuideTHE LIMITATIONS OF THIS ALARM SYSTEM LIMITED WARRANTY Page Page Page Page Page Page Page 165 Eileen Way, Syosset, New York ¬19+lN7001V5 5/04 Rev A