Honeywell K14114 3/06 Rev.B setup guide Device Programming Menu Mode, Programming Options Defined

Page 34

LYNXR-I Installation and Setup Guide

80 Device Programming Menu Mode

Powerline Carrier devices (eg., X10 brand devices) are programmable switches that can be used to perform many different functions. They can be used to turn lights on and off, control sounders, or for status indications. In this system, each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP). Each of these is described below.

The control supports a total of 8 output devices.

The K10145X10 transformer sends signals from the control panel through the premises AC wiring to the Powerline Carrier Devices (which are plugged into AC outlets). Devices plugged into Powerline Carrier Devices can then be made to perform various functions in response to commands entered at the keypads in the security system.

UL

Powerline Carrier Devices have not been evaluated by UL.

 

Programming Options Defined

The following will help you understand the programming of output devices when using 80 and 81 modes.

ACTION The "ACTION" of the device is how the device will respond when it is activated by the "START" programming. There are four different choices of actions:

ACTIVATE for 2 SECONDS and then reset.

ACTIVATE and REMAIN ACTIVATED until stopped by some other event.

PULSE ON and OFF until stopped by some other event.

NOT USED when the device is not used.

START The "START" programming determines when and under what conditions the device will be activated. The following START options are available:

Start by Event

1.Event is the condition (alarm, fault, trouble) that must occur to a zone or group of zones (zone list) in order to activate the device. These conditions apply only when a zone list is used. The different choices for "EVENT" are listed below and in the “Programming Powerline Carrier Devices” paragraph that follows.

• ALARM

Device activates upon any alarm in an assigned zone in the zone list.

• FAULT

Device activates upon any opening or short in an assigned zone in the zone list.

• TROUBLE

Device activates upon any trouble condition in an assigned zone in the zone list.

• NOT USED

Device action is not dependent upon one of the above events.

2.A zone list is a group of zones to which the “EVENT” applies in order to activate a particular device. Note that there are a total of 3 output device-related zone lists that can be programmed in 81 menu mode; when the selected EVENT (alarm, fault or trouble) occurs in any zone in the selected “Start” ZONE LIST (1, 2, or 3), activation of the selected device will START.

Start by Zone Type or System Operation

If a system operation, such as “DISARMING” or “ANY FIRE ALARM,” is to activate the device, the appropriate choice would also be entered under the “ZONE TYPE” option. “ZONE TYPE” is used independently of the “EVENT/ZONE LIST” combination.

If a "ZONE TYPE" is chosen, any zone of that response type going into alarm, trouble, or fault will cause the device to activate as selected in "ACTION.” If the same “ZONE TYPE” is also chosen for the STOP programming, any zone of that type that restores will de-activate the device.

If a "SYSTEM OPERATION" is chosen (e.g., End of Exit Time), that operation will cause the device to activate as selected in "ACTION.” The different choices for "ZONE TYPE" and "SYSTEM OPERATION" are listed in the “Start zone type” paragraphs later in this section, and in the Programming Form.

- 34 -

Image 34
Contents Ademco LYNXR-I Recommendations for Smoke and Heat Detectors Recommendations For Proper Intrusion ProtectionTable of Contents System Features Wall Mounting Mounting the ControlDesktop Mounting Wiring Overview Wiring ConnectionsLYNXR-I Wiring Connections Wiring Connections Full Line Seizure ConnectionsAlarmNet 7845i-L* Communications Device Connecting/Configuring Communication ModulesInstalling the 7845i-L Communications Module GeneralConnecting AlarmNet 7845GSM* / 7845i-GSM Connecting AlarmNet 7845i-ENT/7845iLRR/IP Communications Device 24-Hour Standby Power Connecting AlarmNet 7845CV2AlarmNet 7845CV2 AC Power and Rechargeable Backup Battery AC Power and Backup BatteryBackup battery Distance from TransformerAC Power and Rechargeable Backup Battery Replacing the Rechargeable BatteryGeneral Information Installing Wireless ZonesType Description Enter Installer code 4112 + # + Transmitter Battery LifeUsing the Transmitter Sniffer Mode Go/No Go Test ModeSetting DIP Switches on the 5800RL Transmitter Setting 5800RL DIP SwitchesGeneral Programming Information Entering Program ModeMechanics of Programming Programming a Data FieldInteractive Mode Used to Program Interactive Menu Mode Programming 56, 80, 81, 83, 84Loading Factory Defaults Exiting Program ModeZone Response Type Definitions 5806/5807/5808 Defaults where applicable are Indicated in bold text Data Field DescriptionsDialer Programming Fields 43 Split/Dual Reporting Second Dialer Delay BurglaryEnable/Disable LRR/IP Communications Periodic Test ReportSystem Status and Restore Report Codes Programming 59 76 System Status Report CodesRestore Report Codes Dynamic Signaling Delay/ Dynamic Dynamic Signaling DELAY/DYNAMIC Signaling Priority FieldSignaling Priority = Aux key performs defined function Audio Alarm Verification AAV/RemoteAUX Function/1-Button Paging MacroZone Lists Menu Mode Enhanced Zone Programming ModeDevice Programming Menu Mode Enhanced Sequential ModeEnhanced Zone Programming Mode Report code Zone numberZone type Input typeLoop number or Loop and Serial Delete zone parameters confirmationSerial number Enroll modeVoice descriptor Descriptor Start by Event Device Programming Menu ModeProgramming Options Defined Start by Zone Type or System OperationUpon Restore of a Zone List Programming Powerline Carrier DevicesUpon a Zone Type or System Operation Device number Powerline Carrier DeviceProgramming Device actionZone List Menu Mode Enhanced Sequential Mode IA LC = copy the previous serial number entry from the bufferDelete serial number Assign Zone Voice Descriptors Assign zone voice descriptorsAssign Zone Voice Descriptor Voice Vocabulary IndexAssign custom voice descriptors Record Custom Voice DescriptorsCustom descriptor number Voice Prompt Programming Keypad Functions Voice Prompt ProgrammingDELETE/ Stay key Used to Toenroll Second Central Station Account NumberFront Basement Back Sliding Side Hall Gar ge Kitchen Patio Sensor Type Sensor Location Location ModifiersPendant Type Template selections Template To!Enter Expert Programming ModeTemplate Remote Programming Information Remote Programming/Control DownloadingEquipment required to download to a system at the premises Remote Programming Advisory Notes Security Codes System OperationPanic Keys Message Center Volume ControlKeypad Functions Other FunctionsSpeaker Phone Operation Remote Phone Control FeatureRemote Phone Control Feature Quick Arm NoteOperator Commands Audio Alarm Verification Two-Way Voice FeatureActivation Exit Error Alarm Displays Follow Me System Announcement FeaturePowerline Carrier Devices e.g. X10 devices Display MeaningAlarm System DisplaysArmed System Test Testing the SystemTest Mode Return to normal operationSystem Communication Communication OverviewCode Definition Report +1/4+1 Standard +1/4+1 ExpandedTrouble Conditions Troubleshooting GuideSystem Trouble Displays Symptom Possible Cause Remedy S t e m i n c l u d i n g W i r e l e s sN t r o l Smoke DetectorsProgramming Default Tables Boldface indicates defaults that differ between tablesDefault Duress Code Function Event loggingEvent Start StopDevice Number System OperationIndex House ID Serial Number Federal Communications Commission FCC Part 15 Statement Regulatory Agency StatementsUL Notice This is a Grade a residential system Federal Communications Commission FCC PartLimitations of this Alarm System LYNXR-I SpecificationsRead the Instructions ALL Output Circuits are Power Limited SystemLimited Warranty