American Water Heater VG6250T100 Installation Requirements - Commonwealth of Massachusetts

Page 22
Installation Requirements - Commonwealth of Massachusetts

Installation Requirements - Commonwealth of Massachusetts

Commonwealth of Massachusetts

For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certified.

Signage

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “gas vent directly below. Keep clear of all obstructions.”Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector

observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building, or structure used in whole or in part for residential purposes.

Manufacturer Requirements - Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

Manufacturer Requirements - Gas Equipment Venting System Not Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1.The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2.The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

22

Image 22
Contents RESIDENTIAL GAS WATER HEATERS For Your Safetywhenever maintenance adjustment or service is required Instruction Manualtable of contents APPROVALS safe installation, use and serviceDANGER Improper installation, use and service may result in property damage general safety informationPrecautions Explosion Hazardgeneral safety information Breathing Hazard - Carbon Monoxide Gas General Safety InformationFire or Explosion Hazard Electrical Shock HazardAbbreviations Used Preparing For The Installationintroduction QualificationsGet To Know Your Water Heater - Gas Models features and componentsREPLACEMENT PARTS AND DELIMING PRODUCTS Control AssemblyTable 1 - Rough-In-Dimensions installation considerationRough In Dimensions Table 2 - Capacity, Gas and Electrical CharacteristicsProperty Damage Hazard Locating The Water HeaterInsulation Blankets Combustion Air and VentilationUnconfined Space Outdoor Air Through Two Openings Confined SpaceFresh Air Openings For Confined Spaces Outdoor Air Through One OpeningOutdoor Air Through Two Horizontal Ducts Air From Other Indoor SpacesChemical Vapor Corrosion installing the new water heaterPower Supply Water PipingSpace Heating and Potable Water System Mixing ValvesDishwashing Machines Time to Produce 2nd & 3rdThermal Expansion Closed Water SystemsT & P Valve and Pipe Insulation if supplied Temperature-Pressure Relief Valve Water Damage HazardExplosion Hazard T&P Valve Discharge Pipe RequirementsCondensate Piping Gas PipingSupply Gas Regulator SEDIMENT TRAPSHigh Altitude Installations Filling the Water HeaterIf using 3” inch vent pipe VentingIf using 2” inch vent pipe VENT PIPE TERMINATIONINSTALLATION OF VENT SYSTEM VENT TERMINAL INSTALLATION, SIDEWALLCommonwealth of Massachusetts Installation Requirements - Commonwealth of MassachusettsInstallation of Carbon Monoxide Detectors Approved Carbon Monoxide DetectorsTermination Clearances Sidewall Power Vent POWER VENTTermination Clearances Sidewall Direct Vent Vent Termination - Figure 15A DIRECT VENT terminal installation Installation SequenceSEQUENCE OF INSTALLATIONS, FIGURE 15A Figure 15BVERTICAL VENT TERMINAL INSTALLATION Flat Roof InstallationINSTALLATION PROCEDURE 1 ROOF TERMINATION, see Figure Concentric vent installationSAFETY CONSIDERATIONS Table 6 - KIT COMPONENTSPROCEDURE 2 SIDE WALL TERMINATION, see Figure CONCENTRIC TERMINATION FLAT ROOF CLEARANCEFigure 23A MULTI-CONCENTRIC VENT TERMINATIONS direct vent diagram 1. INITIAL PREPARATION Vent Pipe PreparationRECOMMENDED BRUSH* SIZE FOR PRIMER AND CEMENT APPLICATIONS 2. SELECTION OF MATERIALSSTEP F G. Cleanup and joint movement D. Inspection, cleaning, primingSTEP E F. Joint assembly B. DeburringBLOCKED EXHAUST SWITCH Controls and SwitchesBLOWER PROVER SWITCH BLOCKED INTAKE SWITCHTHIS WATER HEATER IS POLARITY SENSITVE BEFORE APPLYING Power Vent Wiring Schematic - FigureWIRE TO GROUND CHECK INDICATES ZERO VOLTAGE ELECTRICITY TO THIS HEATER BE CERTAIN THAT SUPPLY NEUTRALTO TURN OFF GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE LIGHTINGOPERATING INSTRUCTIONS WARNING TURN OFF ALL ELECTRIC POWER BEFORE SERVICINGTime to Produce temperature regulationHI LIMIT SWITCH ECO 2nd & 3rd DegreeOperating Set Point adjust user settingscontrol system operation 120FDescription IconStatus Icons Operating States StateMenu Control System MenusHELP User Settings & Control System MenusMENU Main Menu140F Heater StatusTemperature Units Display SettingsHeater Information Backlight DelayRestore Factory Defaults Fault HistoryFault Occurrence Blocked ExhaustChange Contact Name Service Contact InformationShow Contact Information Current Contact InfoOperational Conditions for your informationStart Up Conditions SMOKE/ODORAnode Rod Inspection periodic maintenanceVenting System Inspection Temperature-Pressure Relief Valve OperationBurn harzard Hot water discharge ServiceDraining and Flushing Keep hands clear of drain valve dischargemaintenance Temperature-Pressure Relief Valve Testleakage checkpoints Water Heater Location troubleshootingInstallation Checklist VentingSequence Of Operation Flow Chart YESNOBurn Hazard Operational ProblemsFault and Alert Conditions Replacement PartsResetting Control System Lock Outs Electrical Shock HazardDiagnostic Checks Low Igniter Current AC ReversedIgnition Failure Blocked ExhaustBlocked Air Intake Blower Prover FailureBlower Prover Open Energy Cut Out ECOPage Page Page CLAIM PROCEDURE LIMITED RESIDENTIAL GAS WARRANTYSERVICE AND LABOR RESPONSIBILITY CONDITIONS AND EXCEPTIONSPO Box 1597, 500 Princeton Road Johnson City, TN American Water Heater Product Service and SupportCopyright 2011 American Water Heaters. All rights reserved