￿Do not block the airflow from radiator vent or muffler exhaust. It may result in reduced engine performance, overheating, or damage to the electrical parts.

￿Operating in dusty area or salty air (by the ocean), or any other particulate environment may result in clogged radiator, which may cause overheating, other malfunctions and insulation deterioration. Use extreme care, frequent checks and maintenance.

7 Connection

7.1 Selecting Cable

Select the cable with proper gauge, based on its allowable amperage and the distance between the generator and the machinery to be connected.

! Caution

:Electrical damages

￿If the load exceeds the allowable amperage, the overheating may damage the cable.

￿If the cable is either too long or too small a gauge, there will be greater voltage drop to loads, which may result in reduced performance in the connected loads, malfunction, or damages.

<Caution>

It is recommended to select the proper gauge and length of cable, with consideration of the maximum 5% marginal drop only for the rated voltage, between the terminals of loads and generator via the cables.

Expedient Expression: the voltage drop of cables

√3

■ ○

3-Phase 3-Wire

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Length(m)

 

 

Voltage Drop (V) =

 

x

 

x

Current (A) x

 

 

 

 

 

58

 

Gauge(mm2)

 

1-Phase 2-Wire

 

 

 

 

 

 

 

1

 

Length(m)

 

Voltage Drop (V) =

 

x

 

x

Current (A) x 2

 

 

 

 

58

 

Gauge(mm2)

 

- 18 -

Image 18
Contents Table of Contents DG150MI DG250MIIntroduction Electrical Shock Safety GuidelinesSuffocation from exhaust fume InjuriesInjuries to eyes and skin FireBurns Location of Warning labels Alternator Engine SpecificationsSpecification Matrix Control Panel Unit Name of GeneratorParts Ambient ConditionExternal view Control panel NameWater Temperature Monitoring Lamp for temperature High EquipmentMonitor Display Engine Oil Monitoring Lamp for oil pressure low Battery Charge Monitoring Lamp charge lamp Tachometer DG250MI only GaugesFluid Level Monitoring Lamp DG250MI only Hour MeterGenerator Gauges Water Temperature Gauge DG250MI onlyOil Pressure Gauge DG250MI only LampSwitch Voltage Regulator Fuel Line Changeover Valve 3-way valveVoltage Regulator and Throttle Handle Throttle HandleUsing fuel from external fuel tank Transport and InstallationUsing fuel from built-in fuel tank TransportationInstallation TransportationConnection Selecting CableElectrical damages Connecting Cable Load Connection Terminal Plate 3-Phase / 1-phase 2 1-Phase Output Terminals & Receptacles 2.1 2002.2 400 Earth Leakage Relay and Grounding Grounding WorkOperation Check Earth leakage breaker relay has activatedElectrical Shock Injuries Initialization and pre-checkChecking Engine Oil Fire BurnsViscosity and temperature Checking Coolant / WaterEngine Oil Capacity Checking Radiator / Adding water Checking Coolant reservoir tank / Adding coolantTension Checking Fan BeltCoolant Capacity ConditionChecking Fuel Checking Battery Replacing the batteryChecking Fuel, Engine Oil, and Water leakage Operation Initializing / preparationDuring Operation Post startup checkStopping the Generator Protection⑥ Features Adjustment During operationConnecting to External Fuel Tank Protection Feature ListOverload Maintenance Turn the lever for 3-way valve to B positionGenerator side Oil Change Oil Filter ChangeModel Isuzu Part No Cleaning / Changing Air Filter Element Cleaning / Changing Fuel FilterDraining Water from Fuel Tank Changing Coolant / WaterModel Storage Procedures Long-term StorageTroubleshooting StackingSymptoms Possible Cause Corrective Actions Generator Wiring Diagram Page Page Page Engine Wiring Diagram