Shindaiwa DG150MI, DG250MI specifications Earth Leakage Relay and Grounding, Grounding Work

Page 22

7.3Earth Leakage Relay and Grounding

!Danger

:Electrical Shock

￿Ground the every earth grounding terminal to the earth as set out in the manual.

If even one no of all is unconnected by mistake or accident, it will be much more dangerous for human body than the –relay case, because leaking current inevitably goes through the body.

￿Even though all the bonnets of the loads have been grounded to the earth, the earth grounding terminal and the outer bonnet (canopy) grounding terminal should be grounded to the earth.

￿Grounding should be made after the engine is stopped.

￿Whenever the earth leakage breaker relay is activated, you should always repair the leaking place first of all.

The generator is provided with the earth leakage breaker relay to detect any leakage produced due to such the trouble as insulation failure of the load while the generator is running and to cut off the circuit for protection against any accident such as electrical shock resulting from the trouble.

The specification of the earth leakage relay;

￿ Rated Sensitive Current: 30mA (or below) (Grounding resistance: 500￿ or below) ￿ Sensitive time: Within 0.1second

<Caution>

Different sensitivity relay is available to change. But, in the case, consult with our engineering Section, because the value each of grounding resistance and grounding condenser will be different accordingly. In the event bigger value sensitive relay (100, 200, 500mA, etc.) than 30mA will be used in the device, they are too high in value to prevent from electrical shock. Therefore, install each load with the 30mA (or below) relay separately.

The detailed information about sensitive current selection is prepared to give by the article No.151.2

In Earth Leakage Breaker – Selection of The Wiring Regulations issued by Japan Electric Association.

7.3.1 Grounding Work

The qualified electrician should perform the grounding of the following 3 points (500￿ or below).

￿The earth neutral grounding terminal in the output terminal block

￿The Outer Bonnet (Canopy) grounding terminal of the generator

￿The Outer Bonnet of the load

<Caution>

In the event you cannot ground the generator to the earth, consult with the authorized distributor or our engineering section

- 22 -

Image 22
Contents Table of Contents DG150MI DG250MIIntroduction Electrical Shock Safety GuidelinesSuffocation from exhaust fume InjuriesFire Injuries to eyes and skinBurns Location of Warning labels Alternator Engine SpecificationsSpecification Matrix Control Panel Unit Name of GeneratorAmbient Condition PartsExternal view Control panel NameEquipment Water Temperature Monitoring Lamp for temperature HighMonitor Display Engine Oil Monitoring Lamp for oil pressure low Battery Charge Monitoring Lamp charge lamp Tachometer DG250MI only GaugesFluid Level Monitoring Lamp DG250MI only Hour MeterGenerator Gauges Water Temperature Gauge DG250MI onlyOil Pressure Gauge DG250MI only LampSwitch Voltage Regulator Fuel Line Changeover Valve 3-way valveVoltage Regulator and Throttle Handle Throttle HandleUsing fuel from external fuel tank Transport and InstallationUsing fuel from built-in fuel tank TransportationInstallation TransportationSelecting Cable ConnectionElectrical damages Connecting Cable Load Connection Terminal Plate 3-Phase / 1-phase 2.1 200 2 1-Phase Output Terminals & Receptacles2.2 400 Earth Leakage Relay and Grounding Grounding WorkOperation Check Earth leakage breaker relay has activatedElectrical Shock Injuries Initialization and pre-checkChecking Engine Oil Fire BurnsChecking Coolant / Water Viscosity and temperatureEngine Oil Capacity Checking Radiator / Adding water Checking Coolant reservoir tank / Adding coolantTension Checking Fan BeltCoolant Capacity ConditionChecking Fuel Replacing the battery Checking BatteryChecking Fuel, Engine Oil, and Water leakage Operation Initializing / preparationDuring Operation Post startup checkStopping the Generator Protection⑥ Features Adjustment During operationProtection Feature List Connecting to External Fuel TankOverload Maintenance Turn the lever for 3-way valve to B positionGenerator side Oil Filter Change Oil ChangeModel Isuzu Part No Cleaning / Changing Air Filter Element Cleaning / Changing Fuel FilterChanging Coolant / Water Draining Water from Fuel TankModel Storage Procedures Long-term StorageTroubleshooting StackingSymptoms Possible Cause Corrective Actions Generator Wiring Diagram Page Page Page Engine Wiring Diagram