Shindaiwa DG250MI, DG150MI Operation Check, Earth leakage breaker relay has activated

Page 23
Ensure that the breakers and the switches of load(s) are positioned to OFF.
Ensure that the 3-Phase circuit breaker and the 1-Phase circuit breaker are positioned to OFF. Following the procedure in 9-1 Initializing / Preparation , start an engine.
Turn (Push-up) the 3-Phasecircuit breaker (lever) to ON position.
Push the test button (red) in the earth leakage relay unit. When the button is pushed, the earth leakage indicating lamp turns ON and the 3-Phase circuit breaker is positioned in the middle between ON and OFF positions simultaneously, the device works normally.
Push the reset button. The earth leakage indicating lamp (red) turns OFF subsequently. Turn (Push-down) the 3-Phase circuit breaker (lever) to OFF position.

7.3.2Operation Check

!Danger

: Electrical Shock

Before turning the 3-Phase circuit breaker to ON Position, ensure that the breaker or the switch of loads are positioned to OFF.

Operate the 3-Phase circuit breaker, well-communicating with The electrician by the load side.

Before operating the generator, check always if the device can work.

In the event you cannot complete every step of the above procedure to the end, the device is out of order. Consult with our authorized distributor or our engineering section and ask to repair.

7.3.3 The earth leakage breaker relay has activated

In the event the earth leakage breaker relay has activated, the earth leakage indicating lamp Turns ON and the 3-Phase earth leakage breaker (lever) trips off to be positioned in the middle between ON and OFF positions.

In the above condition, even though you stop the engine once and start it again, the 3-Phase Circuit breaker (lever) does not restore to ON or OFF, and the reset button does not function,

because the device keeps detecting current leakage.

Stop the engine promptly and find the leakage point to repair. After repairing the leakage point(s), proceed with the following restoration steps.

(In the case the earth leakage indicating lamp does not turn to ON simultaneously, the cause is Over-Load or Short-Circuit.)

- 23 -

Image 23
Contents DG150MI DG250MI Table of ContentsIntroduction Injuries Safety GuidelinesSuffocation from exhaust fume Electrical ShockBurns Injuries to eyes and skinFire Location of Warning labels Control Panel Unit Name of Generator SpecificationsSpecification Matrix Alternator EngineExternal view PartsAmbient Condition Name Control panelMonitor Display Water Temperature Monitoring Lamp for temperature HighEquipment Engine Oil Monitoring Lamp for oil pressure low Battery Charge Monitoring Lamp charge lamp Hour Meter GaugesFluid Level Monitoring Lamp DG250MI only Tachometer DG250MI onlyLamp Water Temperature Gauge DG250MI onlyOil Pressure Gauge DG250MI only Generator GaugesSwitch Throttle Handle Fuel Line Changeover Valve 3-way valveVoltage Regulator and Throttle Handle Voltage RegulatorTransportation Transport and InstallationUsing fuel from built-in fuel tank Using fuel from external fuel tankTransportation InstallationElectrical damages ConnectionSelecting Cable Connecting Cable Load Connection Terminal Plate 3-Phase / 1-phase 2.2 400 2 1-Phase Output Terminals & Receptacles2.1 200 Grounding Work Earth Leakage Relay and GroundingEarth leakage breaker relay has activated Operation CheckFire Burns Initialization and pre-checkChecking Engine Oil Electrical Shock InjuriesEngine Oil Capacity Viscosity and temperatureChecking Coolant / Water Checking Coolant reservoir tank / Adding coolant Checking Radiator / Adding waterCondition Checking Fan BeltCoolant Capacity TensionChecking Fuel Checking Fuel, Engine Oil, and Water leakage Checking BatteryReplacing the battery Initializing / preparation OperationPost startup check During OperationAdjustment During operation Stopping the Generator Protection⑥ FeaturesOverload Connecting to External Fuel TankProtection Feature List Turn the lever for 3-way valve to B position MaintenanceGenerator side Model Isuzu Part No Oil ChangeOil Filter Change Cleaning / Changing Fuel Filter Cleaning / Changing Air Filter ElementModel Draining Water from Fuel TankChanging Coolant / Water Long-term Storage Storage ProceduresStacking TroubleshootingSymptoms Possible Cause Corrective Actions Generator Wiring Diagram Page Page Page Engine Wiring Diagram