ENGINE OPERATING PANEL
9.
10.Warning Lamp
11.Emergency Stop Lamp
12.Diagnostic Display – This display monitors crtical engine functions. If any abnormal conditions occur, an Active Fault Code will be displayed. This diagnostic display can be located inside the control box.
13.Auto On/Off Engine Controller (MPEC) –
This controller has a vertical row of status LED's (inset), that when lit, indicate that an engine malfunction (fault) has been detected. When a fault has been detected
the engine controller will evaluate the fault and all major faults will shutdown the generator.
During, The MPEC will attempt to crank the engine for 10 seconds before disengaging.
14.Emergency Stop Button – In the event of an emergency, press this button to shutdown the generator.
If the engine does not engage (start) by the third attempt, the engine will be shutdown by the engine controller’s
mode. If the engine engages at a speed (RPM's) that is not safe, the controller will shutdown the
engine by initializing the | mode. |
Also the engine controller will shut down the engine in the event of low oil pressure, high coolant temperature, low coolant level, and loss of magnetic pickup.These conditions can be observed by monitoring the LED status indicators on the front of the controller module.
A.MPEC Control Switch – This switch controls the running of the unit. If this switch is set to the OFF/RESET position, the unit will not run. When this switch is set to the MANUAL position, the generator will start immediately.
If the generator is to be connected to a building’s AC power source via an automatic transfer switch (isolation), place the switch in the AUTO position. In this position, should an outage occur, the automatic transfer switch (ATS) will start the generator automatically via the generator’s
B.Low Oil Pressure – Indicates the engine pressure has fallen below 15 psi. The oil pressure is detected using
variable resistive values from the oil pressure sending
unit. This is considered a | fault. |
C.High Coolant Temperature – Indicates the engine temperature has exceeded 239°F. The engine temperature is detected using variable resistive values
from the temperature sending unit. This is considered
a fault.
D.Overcrank Shutdown – Indicates the unit has attempted to start a pre- programmed number of times, and has failed to start. The number of cycles and duration are programmable. It is
a 10 second duration.This is considered a | fault. |
E.Overspeed Shutdown – Indicates the engine is running at an unsafe speed.This is considered a fault.
F.Engine Running – Indicates that engine is running at a safe operating speed.