GENERATOR SHUT-DOWN PROCEDURES
WARNING - SHUTTING DOWN THE
GENERATOR
NEVER stop the engine suddenly except in an emergency.
CAUTION - DIAGNOSTIC SWITCH
ALWAYS make sure the diagnostic switch is placed in the OFF position before attempting to shut down the generator. The OFF/RESET switch on the MEC controller will not shut down the generator if the diagnostic switch is left in the ON position.
Normal Shutdown Procedure
To shutdown the generator use the following procedure:
1.Place both the MAIN, GFCI and LOAD circuit breakers as shown in Figure 40 to the OFF position.
2.Place the engine speed switch (Figure 58) in the “ ” (down) position.
Figure 58. Engine Speed Switch (Low)
3.Let the engine cool by running it at low speed for
4. Place the | (Figure 59) to the |
OFF/RESET position. |
|
Emergency Shutdown Procedure
To shutdown the generator in the event of an emergency use the following procedure:
1. Place the | (Figure 59) in the |
OFF/RESET position. |
|
Figure 59. MPEC Control Switch (Off/Reset)
5. Verify that the |
| status LED on the MPEC display |
are OFF (not lit). |
|
6.Remove all loads from the generator.
7.Inspect entire generator for any damage or loosening of components that may have occured during operation.
PAGE 56 —