- INSTALLATION MANUAL -
| Parameter | Description |
| Default | Default | min | MAX | |
|
| (BCF...) | (BC...) | |||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| CONFIGURATION |
|
|
|
|
|
|
| C01 | Door input (0 |
| 1 | 1 | 0 | 1 |
|
| C02 | Door open polarity |
| 0 | 0 | 0 | 1 |
|
| C03 | Door open alarm delay |
| 2 min | 2 min | 0 min | 60 min | |
| C04 | Activates buzzer (0 |
| 1 | 1 | 0 | 1 |
|
| C05 | Buzzer duration at the end of quick cooling cycle |
| 10 sec | 10 sec | 0 | 600 sec | |
| C06 | Temperature difference in the first phase of needle insertion |
| 13°F | 45°F | 0 | 140°F | |
| test (0 = test excluded) |
| ||||||
|
|
|
|
|
|
|
| |
| C07 | Duration of the second phase of needle insertion test (0=test |
| 56 sec | 56 sec | 0 | 600 sec | |
| excluded) |
| ||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| Activates condenser probe |
|
|
|
|
|
|
| C08 | 0 = no probe |
| 1 | 1 | 0 | 1 |
|
|
| 1 = probe |
|
| ||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| C09 | Compressor stop delay due to door opening |
| 30 sec | 30 sec | 0 sec | 60 sec | |
| C10 | Control pressure alarm detection time |
| 5 sec | 5 sec | 0 sec | 60 sec | |
| C11 | High pressare digital input polarity |
| 0 | 0 | 0 | 1 |
|
| C12 | Resistances starting SetPoint |
| 23°F | 23°F | 14°F | 68°F | |
|
| ADJUSTMENT |
|
|
|
|
|
|
| R01 | Compressor start/stop hysteresis |
| 5°F | 38°F | 0°F | 36°F | |
| R02 | Min. interval between 2 compressor starting |
| 2 min | 2 min | 0 min | 30 min | |
| R03 | Compressor start delay from card activation |
| 0 sec | 0 sec | 0 sec | 300 sec | |
| R04 | Compressor |
| 10 min | 10 min | 0 min | 90 min | |
| R05 | Compressor ON time faulty room in pos. storing |
| 3 min | 3 min | 0 min | 90 min | |
| R06 | Compressor ON time with faulty room in neg. storing |
| 8 min | 8 min | 0 min | 90 min | |
| R07 | Needle min. temperature for starting quick cooling |
| 158°F | 158°F | 32°F | 194°F | |
| R08 | Compressor block temperature |
| 194°F | 194°F | 32°F | 212°F | |
| R09 | Compressor Protection function activation time |
| 24 hour | 24 hour | 0 hour | 240 hour | |
| R10 | Pulse duration |
| 2 sec | 2 sec | 1 sec | 10 sec | |
| R11 | Pause between pulses |
| 8 sec | 4 sec | 1 sec | 10 sec | |
| R12 | Number of pulses |
| 3 | 3 | 1 | 20 |
|
| R13 | Temperature at the end of the Cooling cycle |
| 50°F | ||||
|
| FANS |
|
|
|
|
|
|
| F01 | Evaporator fans activation hysteresis |
| 4°F | 36°F | 0°F | 36°F | |
| F02 | Condenser fans activation hysteresis |
| 4°F | 36°F | 0°F | 36°F | |
| F03 | Evaporator fans activation SetPoint |
| 41°F | 41°F | 122°F | ||
| F04 | Condenser fans activation SetPoint |
| 59°F | 59°F | 122°F | ||
| F05 | Evaporator fans during defrost |
| 0 | 0 | 0 | 1 |
|
| 0 = fans OFF; 1 = fans ON |
|
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| F06 | Condenser fans during defrost |
| 0 | 0 | 0 | 1 |
|
| 0 = fans OFF; 1 = fans ON |
|
| |||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| |
| F07 | Fans stop time after defrost |
| 1 min | 1 min | 0 min | 30 min | |
| F08 | Condenser fans stop delay |
| 30 sec | 30 sec | 0 sec | 300 sec | |
|
| Evaporator fans control during quick cooling: |
|
|
|
|
|
|
| F09 | 0 = fans always ON |
| 0 | 0 | 0 | 1 |
|
|
| 1 = fans thermostated by evaporator temperature |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Evaporator fans control during storing: |
|
|
|
|
|
|
| F10 | 0 = fans in parallel with the compressor |
| 0 | 0 | 0 | 1 |
|
|
| 1 = fans thermostated by evaporator temperature |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| F11 | Evaporator fans block temperature |
| 158°F | 158°F | 32°F | 194°F | |
|
|
|
|
|
|
|
| |
| PR1 | Sampling time |
| 10 min | 10 min | 1 min | 60 min | |
|
| VENTILATION SPEED (P.W.M.) |
|
|
|
|
|
|
| CF1 | Evaporator fan min. speed |
| 30 | 20 | 0 | 100 |
|
| CF2 | Evaporator fan min. speed selectable in a quick cooling cycle |
| 50 | 50 | 0 | 100 |
|
|
|
|
|
|
|