25
PP-32
KOOLMASTER PP-32 REV.01
2. Static pressure set points' transition according to the outside T°:
Example: When the outside temperature drops below the "outside
temperature influence" value, a transition between the two set
point groups starts. When the outside temperature decreases
5°F further than the user-defined value, the second group of
set points is used.
Refer to the installation setup section to activate the second group of
static pressure set points (see sec. 5.14.3).
STATIC PRESSURE SET POINTSINFLUENCED BY THE OUTSIDE TEMPERATURE
OUTSIDE
TEMPERATURE
STATIC
PRESSURE
SET POINTS
HI SET POINT 2
(OPEN AT)
HI SET POINT 1
(OPEN AT)
LO SET POINT 2
(CLOSE AT)
LO SET POINT 1
(CLOSE AT)
5°F
(2.8°C)
50°F
(27.8°C) 55°F
(30.6°C)
(outside t° influence)