5.13.2.1 Adjusting Hi/ Lo Temperature Alarms

The low alarm temperature can be adjusted from 20°F to 0.5°F (11.1 to
0.3°C) below the set point

(Lo Offset)

. The high alarm temperature can
be adjusted from 0.5°F to 20°F (0.3 to 11.1°C) above the set point

(Hi

Offset)

. The offset is the number of degrees above or below the set
point at which an alarm is set off.
Set the function to "21.Alarm Limits" from the main menu using the
navigation buttons then press the right-arrow key.
Press the right-arrow key once again, in to select the "1.Tempera-
ture" menu. Lo and Hi Offsets are displayed.
Use the adjustment buttons to set
the Lo and Hi offsets to the desired
values.
ROOM
TEMPERATURE
SP + HI Offset
Critical Alarm
Set Point - Lo Offset
Outside
Influence
NORMAL RANGE: NO TEMPERATURE ALARMS
OUTSIDE THE RANGE: THE TEMPERATURE ALARM IS SET OFF
ALARM LIMIT
OUTSIDE TEMP.
TIME
ALARM DETECTION WITH OUTSIDE T° INFLUENCE
Temperature Alarm
Lo Offset T° 10.0
Hi Offset T° 15.0
Critical 95.0°F