Open Time: when the static pressure exceeds the Hi pressure set point,
the curtain opens during this delay. It ranges from 0 to 900 seconds.
Close Time: when the static pressure drops below the Lo pressure set
point, the curtain closes during this delay. It ranges from 0 to 900 sec.
Off Time: once the curtain has opened or closed (depending on the
situation) it then stops operating during this delay. The Off Time delay
ranges from 0 to 900 seconds.
Select "9.Tunnel Curtain" from the main menu using the navigation
buttons then press the right-arrow key. Note that this menu is only
available if the tunnel curtain has been enabled during the installation
setup (see sec 5.14.3).
Press the right-arrow key once to select "1.Set Points" menu.
Press the down-arrow key in order
to select the "Open Time" display.
Use the adjustment buttons to
adjust the Open Time. Note that
this menu only appears if the
curtain operates in static pressure
mode (see sec 5.14.3).
Press the down-arrow key in once. The Close Time is selected. Use
the adjustment buttons to set the Close Time to the desired value.
Press the down-arrow key in once. The Off Time is selected. Use the
adjustment buttons to set the Off Time to the desired value.
Open At: .080WC
Open Time 60sec
Close Time 60sec
Off Time 10sec
CURTAIN'S TIMER
ON
OPEN / CLOSE
TIMES
OFF
TIME
OFF