8. Adjust the temperature set point. This is the target temperature in
the room. Refer to section 5.3.
9. Adjust the start/stop temperature of fan stages (see sec. 5.7) and
heater stages (see sec. 5.8).
10. Adjust the minimum ventilation cycle settings (see sec. 1.1.1).
11. If inlets operate using DWR-F-1A modules, set the air inlet compen-
sation. This feature helps to reduce temperature differences in the
building (see sec. 5.5.1).
12. Adjust all vent door parameters, if applicable (see sec 5.5.2).
13. Adjust all tunnel curtain settings, if applicable (see sec 5.6).
14. Calibrate the water counter, if applicable (see sec. 5.14.7).
15. Enable the desired options to control the humidity level in the barn
(see sec. 5.15.3).
16. Adjust and activate the temperature curve (optional). This feature
allows the temperature set point to be automatically adjusted over
time (see sec. 5.15.1).
17. Adjust and activate the minimum ventilation curve (optional). This
feature allows fans' On-Time, in minimum ventilation, to be auto-
matically adjusted over time (see sec. 5.15.2).
18. Adjust start/stop times of each clock output. These outputs allow to
operate various devices according to timer cycles (see sec. 5.11).
19. Adjust start/stop temperatures of each auxiliary output. These
outputs allow to operate various devices according to the room
temperature (see sec. 5.9).
20. Adjust the animal age (see sec. 5.10). To clear previous histories,
the animal age must first be set to "Off" and then be changed for
"1 day".