87
PP-32
KOOLMASTER PP-32 REV.01
Use the adjustment buttons to set the humidity level that will be
added or removed from all readings of the humidity sensor.
5.15.4.3 Calibrating the Static Pressure Level
The reading of the static pressure level can adjusted by an amount of
±0.030"WC (±7Pa).
Select "8.Vents/Static P" from the
main menu using the navigation
buttons then press the right-arrow
key. The calibration menu flashes
on the display "Cal. SP". Note that
this menu is only available if the
static pressure sensor has been enabled during the installation setup
and in the installer mode (see sec. 5.14.2 and 5.14.3).
Use the adjustment buttons to set the humidity level that will be
added or removed from all readings of the humidity sensor.
Vents/Static Press
Cal. SP .000WC
Close At: .070WC
Open At: .090WC