KOOLMASTER PP-32 REV.01
Press the down-arrow key to select the Hi alarm limit.
Use the adjustment buttons to set the Hi alarm limit to the desired
value.
Note : If you do not want a relay to be turned off in the case of a low
static pressure alarm, set the Low Alarm limit to "
Off
" by
pressing the down-arrow key.
Adjusting High/Low Delays
Set the function to "21.Alarm Limits" from the main menu using the
navigation buttons then press the right-arrow key.
Use the navigation buttons to select "2.Static Pressure" then press
the right-arrow key.
Press the right-arrow key once again in order to select the "1.Hi/Lo
limits" option. The Lo and Hi pressure limits are displayed.
Press the down-arrow key in order
to select the "Lo Delay" display.
Use the adjustment buttons to set
the Lo Pressure Alarm Delay to the
desired value.
Press the down-arrow key once again to select the "Hi Delay" display.
Use the adjustment buttons to set the Hi Pressure Alarm Delay to
the desired value.
Low Alarm .030WC
Hi Alarm .150WC
Lo Delay 60sec
Hi Delay 300sec