86
PP-32
KOOLMASTER PP-32 REV.01

5.15.4 Calibrating Sensors

The reading of each sensor can be slightly adjusted by the user in order
to obtain the most accurate and uniform readings of all sensors. The
calibration of sensors can only be preformed in the installer mode (see
sec. 5.14.2).
5.15.4.1 Calibrating Room and Outside T° Sensors
The reading of each temperature sensor can adjusted by an amount of
±3°F (±1.7°C).
Set the function to "3.Temp. Sensors" from the main menu using the
navigation buttons. Sensors' temperature readings are displayed.
Use the down-arrow key to select
the calibration menu of a room
temperature sensor or of the
outside temperature sensor

(Cal.Sens.x or Cal.Out)

. Note that
these menus are only displayed in
the installer mode (see sec. 5.14.2).
Use the adjustment buttons to set the temperature that will be
added or removed from all readings of the selected sensor.
5.15.4.2 Calibrating the Relative Humidity Sensor
The reading of the humidity sensor can adjusted by an amount of ±3%.
Set the function to "4.R. Humidity" from the main menu using the
navigation buttons then press the right-arrow key. The current
relative humidity level is displayed. Note that this menu is only
accessible if a humidity sensor has been enabled (see sec. 5.14.3).
Press the down-arrow key once in
order to select the calibration menu
of the humidity sensor "Cal. RH".
Note that this menu is only dis-
played in the installer mode (see
sec. 5.14.2).
Temperature Sensors
Sensor 1: 72.3°F
Cal.Sens.1 0.0°F
Sensor 2: 73.0°F
Relative Humidity
Current RH Low %
Cal. RH 0%
Min/Max Recorded