29
PP-32
KOOLMASTER PP-32 REV.01
Static Settings 2
Outside Temperature
Influence: 50.0°F
Close At: .070WC
Open At: .090WC
Use the adjustment buttons to select the fan stage above which the
second group of static pressure set points starts being used.
Press the down-arrow key once, the LO static pressure set point #2
is selected
(Close At)
.
Use the adjustment buttons to adjust the 2nd low static pressure set
point
(Close At)
to the desired value then press the down-arrow key.
The HI static pressure set point #2

(Open At)

is selected.
Use the adjustment buttons to adjust the 2nd HI static pressure set
point
(Open At)
to the desired value.
Press the left-arrow key to exit this menu.
5.5.2.5 2nd Group of Pressure Set Points: at Outside T° X
The following procedure shows how to select the outside temperature
below which the second group of static pressure set points starts being
used. It also explains how to adjust the second group of Hi and Lo static
pressure set points

(Open At and Close At)

. Refer to sec.5.14.3 to
activate this function.
Select "8.Vents/Static P" from the main menu using the navigation
buttons then press the right-arrow key. Note that this menu is only
available if the static pressure sensor has been enabled during the
installation setup (see sec 5.14.3).
Press the right-arrow key to select the "1.Set Points" menu.
Press the down-arrow key in order
to the select "Outside Temperature
Influence" display. Note that this
menu only appears if the outside
temperature has been enabled
during the installation setup and if
the 2nd Group of static pressure set
points has been enabled (see sec
5.14.3).