63
PP-32
KOOLMASTER PP-32 REV.01
5.14.3 Installation Setup
The following section describes how to customize the controller for your
particular application. Normally, this setup needs to be done only once.
Parameters are presented below in the order they appear on the display.
Use the adjustment buttons to adjust a parameter value. When you are
finished adjusting a parameter, press the down-arrow key to move to the
next parameter. The user should step through all the parameters at least
once. These parameters are located in the "19.Installation" main menu.
Note that this menu is only accessible on the installer mode (see sec.
5.14.2).
1. Clear Alarms:
Set to "Yes" to reset the alarm log.
2. Reset Time:
Set the time at which minimum and
maximum readings of all sensors are
logged into the history.
3. Use RH?:
Set to "Yes" if a humidity sensor is
connected to the controller.
4. Pre-Open Vent Door Delay:
Set the pre-opening delay of vent doors to the desired value. This
delay can be adjusted from 0 to 60 seconds. Note that this menu only
appears if the static pressure sensor is enabled on #8 below
5. Pre-Open Tunnel Delay:
Set the pre-opening delay of the tunnel curtain to the desired value.
This delay can be adjusted from 0 to 30 seconds. Note that this menu
only appears if the tunnel is enabled on #6 below.
6. Use Tunnel ?:
Set to "Yes" to enable the tunnel ventilation mode.
7. Tunnel Mode:
Select either the tunnel curtain is controlled in timer mode

(Timer)

or
by the static pressure level

(SP)

. This menu only appears if the tunnel
is enabled on #6 above.
Installation
Clear Alarms? No
Reset Min/Max 11:00A
Use RH? Yes
PreOpenVents sec 10
PreOpen Tun sec 30
Use Tunnel ? Yes
Tunnel Mode: SP