INSTALLATION
Check the appliance is electrically safe and gas sound when you have finished.
Stick on label
Stick the “NOW ADJUSTED FOR LP GAS” label next to the ratings label inside the drawer cavity to indicate the gas the appliance is now set for
Pressure Testing
Connect the appliance to the gas supply. Check the appliance is gas sound.
The gas pressure can be measured at the pressure test point on the appliance side of the pressure regulator
For proper operation, the pressure of LP supplied to the regulator must be between 10’’ and 13’’ of water column (2.49 - 3.24 kPa).
When checking for proper operation of the regulator, the inlet pressure must be at least 1’’ (0.25 kPa) greater than the operating (manifold) pressure as given above.
The pressure regulator located at the inlet of the range manifold must remain in the supply line regardless of whether natural or LP gas is being used.
Type 1 | Type 2 |
ArtNo.102-0009 - Gas regulator settings
ArtNo. | - Pressure test point |