Allen-Bradley 160-Series AC Drives

160 Series Drive Control Logic Chart

The following truth table (Tables 26 - 30) designates the preset speed selection based on the inputs to the control terminals. A disconnected control terminal will seek the high signal voltage condition (greater than 10V DC).

Pocket Hardmount

V Control and A control

To activate a control input (i.e., SW1, SW2, etc.), the terminal is connected to a common terminal (TB3-3 or TB3-7) to lower the signal voltage to a low condition (less than 1 Volt DC).

H – Control Voltage High (greater than 10V DC)

 

 

 

 

 

 

 

 

 

0 = No signal received

 

 

L – Control Voltage Low (less than 1V DC)

 

 

 

 

 

 

 

 

 

 

1 = Signal received

 

 

 

 

SW3

SW2

SW1

STF

Stop

STR

 

 

 

 

 

 

 

 

 

 

 

 

 

Preset Status –

Input Status –

DC Volt Meter Red Probe Terminal Location

4

2

1

6

8

5

 

Parameter 15

 

Parameter 12

DC Volt Meter Black Probe Terminal Location

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

Terminal

Terminal

Terminal

Terminal

Terminal

Terminal

UsedNot

 

SW3

 

SW2

SW1

UsedNot

 

STF

Stop

STR

Action

Preset

#4

#2

#1

#6

#8

#5

 

 

 

 

 

 

 

 

 

 

 

 

Parameter #

(SW3)

(SW2)

(SW1)

(STF)

(Stop)

(STR)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Idle

N/A

H

H

H

H

L/H

H

0

 

0

 

0

0

0

 

0

0/1

0

1/2 Wash Speed Forward

62

H

H

L

L

L

H

0

 

0

 

0

1

0

 

1

1

0

1/2 Wash Speed Reverse

62

H

H

L

H

L

L

0

 

0

 

0

1

0

 

0

1

1

Wash Speed Forward

63

H

L

H

L

L

H

0

 

0

 

1

0

0

 

1

1

0

Wash Speed Reverse

63

H

L

H

H

L

L

0

 

0

 

1

0

0

 

0

1

1

Distribution Speed

65

L

H

H

L

L

H

0

 

1

 

0

0

0

 

1

1

0

Spin 1

64

H

L

L

L

L

H

0

 

0

 

1

1

0

 

1

1

0

Spin 2

67

L

L

H

L

L

H

0

 

1

 

1

0

0

 

1

1

0

Spin 3

66

L

H

L

L

L

H

0

 

1

 

0

1

0

 

1

1

0

Pocket Hardmount

WE-6 Control - Design 5 and Earlier

H – Control Voltage High (greater than 10V DC)

 

 

 

 

 

 

 

 

 

0 = No signal received

 

 

L – Control Voltage Low (less than 1V DC)

 

 

 

 

 

 

 

 

 

 

1 = Signal received

 

 

 

 

SW3

SW2

SW1

STF

Stop

STR

 

 

 

 

 

 

 

 

 

 

 

 

 

Preset Status –

Input Status –

DC Volt Meter Red Probe Terminal Location

4

2

1

6

8

5

 

Parameter 15

 

Parameter 12

DC Volt Meter Black Probe Terminal Location

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

Terminal

Terminal

Terminal

Terminal

Terminal

Terminal

UsedNot

 

SW3

 

SW2

SW1

UsedNot

 

STF

Stop

STR

Action

Preset

#4

#2

#1

#6

#8

#5

 

 

 

 

 

 

 

 

 

 

 

 

Parameter #

(SW3)

(SW2)

(SW1)

(STF)

(Stop)

(STR)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Idle

N/A

H

H

H

H

L/H

H

0

 

0

 

0

0

0

 

0

0/1

0

1/2 Wash Speed Forward

65

L

H

H

L

L

H

0

 

1

 

0

0

0

 

1

1

0

1/2 Wash Speed Reverse

65

L

H

H

H

L

L

0

 

1

 

0

0

0

 

0

1

1

Wash Speed Forward

63

H

L

H

L

L

H

0

 

0

 

1

0

0

 

1

1

0

Wash Speed Reverse

63

H

L

H

H

L

L

0

 

0

 

1

0

0

 

0

1

1

Distribution Speed

62

H

H

L

L

L

H

0

 

0

 

0

1

0

 

1

1

0

Medium Extract/Spray Rinse

67

L

L

H

L

L

H

0

 

1

 

1

0

0

 

1

1

0

High 1 Extract

66

L

H

L

L

L

H

0

 

1

 

0

1

0

 

1

1

0

High 2 Extract

64

H

L

L

L

L

H

0

 

0

 

1

1

0

 

1

1

0

High 3 Extract

68

L

L

L

L

L

H

0

 

1

 

1

1

0

 

1

1

0

Table 26

42

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

F232120