| Fault | Description | Corrective Action/ |
| Remarks | ||
|
|
| |
|
|
|
|
03 | Power Loss Fault | DC Bus voltage remains below | Monitor incoming AC line for low voltage or line power |
|
| 85% nominal for longer than .5 | interruption. |
|
| seconds. |
|
|
|
|
|
04 | Under Voltage Fault | DC Bus voltage fell below | Monitor AC incoming AC line for low voltage or line |
|
| minimum. | power interruption. |
|
|
|
|
05 | Over Voltage Fault | DC Bus maximum voltage | Monitor the AC line for high line voltage or transient |
|
| exceeded. | conditions. High voltage can result from motor |
|
|
| regeneration. Buck transformer may be required. |
|
|
|
|
06 | Motor Stall | Motor has stalled. Motor load is | Check motor wiring and connection terminals. Check wash |
|
| excessive. | basket freedom of movement and excess belt tension. |
|
|
|
|
07 | Motor Overload Fault | Internal electronic overload trip. | Check motor wiring and connection terminals. Check wash |
|
| Excessive motor load exists. | basket freedom of movement and excess belt tension. |
|
|
|
|
08 | Over Temperature Fault | Excessive heat detected by | Clear blocked or dirty heatsink fins. Check ambient |
|
| heatsink transducer. | temperature. Check for blocked or nonoperating fan. |
|
|
|
|
10 | Serial Fault | Drive lost communication with | HIM removed while power applied, cycle power to clear. |
|
| controlling device. |
|
|
|
|
|
12 | Overcurrent Fault | Overcurrent detected in | Check short circuit at the controller output or excessive |
|
| instantaneous hardware trip circuit. | load conditions at motor. |
|
|
|
|
22 | Controller Reset Fault | Stop input not present. | Check stop input into control terminal board. Close door |
|
|
| and ensure any jumpers are placed correctly. |
|
|
|
|
32 | EEPROM Fault | EEProm has invalid data. | Consult the factory for further instructions. |
|
|
|
|
33 | Max Retries Fault | Controller failed to reset fault | Fault exists that must be corrected before further operation. |
|
| within the number of retries. | Check “Fault Buffer 1” on 1305 and 1336 for specific fault |
|
|
| that triggered max retries fault. |
|
|
|
|
38 | Phase U Fault | Check wiring between the drive and motor. Check for | |
|
| between controller and motor in | grounded phase. |
|
| Phase U. |
|
|
|
|
|