Power Terminal Block Description

Input and output power connections are performed through a ten-position terminal block, TB1. Refer to Figure 39.

GRD GRD L1

L2

L3

+DC BRK 1

T1

T2

T3

 

 

 

 

 

 

 

 

R

S

T

(-DC)

U

V

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To Motor

To

 

 

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protected AC Input

 

 

 

 

 

 

 

 

 

 

 

 

 

U082ME3A

 

 

 

 

 

 

 

 

 

 

 

 

U082ME3A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 39

 

 

Power Block Terminal (TB1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminals

 

Description

GRD

 

 

 

 

Earth Ground

 

 

R, S, T (L1, L2, L3)

 

AC Input Line Terminals

 

 

 

 

 

 

 

 

 

 

 

 

+DC, BRK (or -DC)

 

Dynamic Brake Option – Refer

 

 

 

 

 

 

 

to instructions with option

U, V, W (T1, T2, T3)

 

Motor Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 37

 

 

Torque Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal

 

Screw

 

Max/Min Wire

 

 

Max/Min

 

Size

 

Size mm2

 

 

Torque

 

 

 

 

 

(AWG)

 

 

N-m (lb-in)

 

 

 

 

 

 

 

 

 

TB1 (0.37 to

 

M4

 

3.5/0.75

 

 

 

0.90

0.75 kW

 

 

 

 

(12/18)

 

 

 

(8)

1/2 to 1 HP)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB1 (All

 

M4

 

4/0.75

 

 

 

1.81

except above)

 

 

 

 

(10/18)

 

 

 

(16)

 

 

 

 

 

 

 

 

 

 

 

 

 

TB2 (All)

 

M3.5

 

1.5/0.20

 

 

 

0.90

 

 

 

 

 

 

 

(14/24)

 

 

 

(8)

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 38

Allen-Bradley 1305-Series AC Drives

Control Terminal Blocks Description and Control Logic

Control terminal functions are unique to each Allen- Bradley Drive. Each drive’s control terminal is addressed independently.

Control Terminal Block (TB2) Function

WARNING

To reduce risk of electric shock, severe injury or death, allow machine power to remain off for three minutes minimum prior to working in and around AC drive. Proceed with caution.

W662

CAUTION

The controller is supplied with an internal 5V supply. Dry contacts or open collectors are required for discrete control inputs. If an external voltage is applied, component failure could occur.

W670

Input Mode Parameter

The control terminal functions are determined in part by the Input Mode parameter #21. Changing this parameter affects the function of some terminals. All machines equipped with 1305 drives use Input Mode “UNIMAC”.

NOTE: If the Input Mode is changed, power must be cycled to the drive for the change to take effect.

Speed Selection

Motor speeds are controlled by solid state or mechanical switch closure inputs to SW1, SW2 and SW3 in conjunction with STR and STF (direction) inputs. Refer to Figure 40 and Table 39.

Table 44 designates the preset speed selection based on the inputs to the control terminals. A disconnected control terminal will seek the high control voltage condition (approx. 5 Volts DC). To activate a control input (i.e., SW1, SW2, etc.), the terminal is connected to a common terminal (TB2-7, TB2-12, or TB2-15) to lower the control voltage to a low condition (less than 1 Volt DC).

F232120