Allen-Bradley 1305-Series AC Drives

Table 45 (continued)

Allen-Bradley Drive Fault Codes (continued)

 

Fault

Description

Corrective Action

 

Remarks

 

 

 

 

 

 

 

39

Phase V Fault

Phase to ground fault detected

Check wiring between the drive and motor. Check for

 

 

between controller and motor in

grounded phase.

 

 

Phase V.

 

 

 

 

 

40

Phase W Fault

Phase to ground fault detected

Check wiring between the drive and motor. Check for

 

 

between controller and motor in

grounded phase.

 

 

Phase W.

 

 

 

 

 

41

UV Short Fault

Excessive current has been

Check motor and external wiring to the controller output

 

 

detected between two controller

terminals for shorted condition.

 

 

output terminals.

 

 

 

 

 

42

UW Short Fault

Excessive current has been

Check motor and external wiring to the controller output

 

 

detected between two controller

terminals for shorted condition.

 

 

output terminals.

 

 

 

 

 

43

VW Short Fault

Excessive current has been

Check motor and external wiring to the controller output

 

 

detected between two controller

terminals for shorted condition.

 

 

output terminals.

 

 

 

 

 

44

IPM Current Fault

Internal power module overcurrent

Check for short circuit at the drive output or excessive load

 

 

limit exceeded.

conditions at the motor, specifically cable capacitance to

 

 

 

ground.

 

 

 

 

45

IPM Overtemp Fault

Internal power module thermal

Check for blocked or dirty heatsink fins. Check ambient

 

 

limit exceeded.

air. Check fan operation or filter blockage.

 

 

 

 

48

Reset to Default Values

Parameters were reset to the

Verify and re-load the desired parameters.

 

 

factory default values.

 

 

 

 

 

Table 45

82