Figure 2-8: Parallel Configuration for Increased Capacity (Four UPSs)

These configurations have an external System Bypass Cabinet (SBC).

PCA INTN

PCA INTN

UPS 1

UPS 2

 

Blue

 

plug

20

20

SBC

 

Interconnections with the external system bypass cabinet (20):

Interconnect terminals 7, 8, 9, and 10 on the auxiliary terminal block TB2 in the system bypass cabinet to UPS terminal blocks XMS04/XMS05 pins 1, 2, 3, and 4 respectively.

Create a loop connection between the cabinet and the UPSs as shown in Figure 2-8.

Details of terminal block connections.

 

 

 

 

 

 

TB2

7

8

 

9

 

10

 

 

20

20

 

 

UPS 4

 

UPS 3

 

 

Red

4

3

2

1

 

 

 

Common

SBC

XMS04 /

XMS05

 

 

 

 

 

 

TB2

7

 

 

1

 

 

 

 

 

8

 

 

2

 

 

 

 

 

 

9

 

 

3

 

 

 

 

 

 

10

 

 

4

 

 

 

 

 

 

 

 

plug

 

 

 

 

19

19

21

21

19

19

21

21

UPS 1

UPS 2

 

Blue

 

plug

UPS 4

UPS 3

 

Red plug

Note: The interconnection cables for the SBC are not supplied

Exchange-current interconnections (19): Use the XMS02 and XMS03 connectors to create a loop between the UPSs (all the XMS02 and XMS03 connectors must be used).

CAN // interconnections (21): Daisy-chain the UPSs using the XMS06 and XMS07 connectors. Fit a blue plug on the first UPS unit and a red plug on the last UPS (all the XMS06 and XMS07 connectors must be used).

Note: The supplied cables are 33 ft long. To ensure sufficient isolation of exchange-current, CAN and external bypass cabinet cables, they must be run separately from the power cables.