Figure 2-15: Routing the Control/Communications Cables for Parallel UPS

Separate the control and communication cables from the power cables.

Run the cables together in front of the protection panels and tie them to the panels as indicated.

Parallel-connection cables for connection to the SBC (not supplied). The CAN and current exchange cables are supplied.

Free slots for optional communication cards. See installation drawing for proper card placement.

Slot for relay communications card

Ties

General-shutdown cable (not supplied) and external battery circuit breaker cable must be tied down separately.

Ties

Cable description

Insulation level

Location on illustration

 

 

 

External bypass cabinet cable

ELV

1

 

 

 

CAN cables

SELV

1

 

 

 

Exchange-current cables

SELV

1

 

 

 

Relay communication card

SELV

3

 

 

 

Optional communication card

SELV or LV

4

 

 

 

External battery circuit-breaker cables

SELV

6

 

 

 

General-shutdown cable

SELV

7

 

 

 

CAUTION To ensure sufficient isolation of exchange-current, CAN and external bypass cabinet cables, they must be run separately from the power cables. Reinforce the insulation of these control and communication cables if any risk of contact with the power cables exists.

2 — 12

Setup and Installation

86-174010-00 B00

Page 34
Image 34