Operation

CAUTION All operations concerning system start-up and compliance with standards and regulations, including those related to the battery cabinet, must be carried out by trained and certified personnel before using the UPS.

3.0Scope

Provides startup, shutdown, and normal operation of the MGE Galaxy 5000 UPS. Describes the operation of the mimic-panel LEDs.

3.1Shutting Down a Single UPS

The UPS remains energized unless it is shut down.

Figure 3-1: Shutting Down a Single UPS

1 - Press a button to exit sleep mode.

2 - Press the OFF button (38) for 3 seconds.

The load is no longer protected by the UPS. It is supplied via the bypass.

3 - Set the battery circuit breaker of the auxiliary cabinets to OFF.

4 - Set the input switch Q1 (8) to OFF.

The charger no longer operates to keep the batteries fully charged.

5 - Open the upstream circuit breakers of the Normal AC source and Bypass AC source to completely power off the UPS.

86-174010-00 B00

Operation

3 — 1

Page 35
Image 35
APC 40 130KVA user manual Operation, Shutting Down a Single UPS