APC 40 130KVA Characteristics of the input contacts, Communications Card Connection Example

Models: 40 130KVA

1 76
Download 76 pages 38.78 Kb
Page 32
Image 32

MGE Galaxy 5000

2.8.1Characteristics of the Contacts on the Relay Communications Card

Figure 2-13: Characteristics of the Contacts on the Relay Communications Card

Low battery warning

Load on battery power

Load on automatic bypass

Load on UPS

Battery fault

General alarm

Characteristics of the output contacts: Permissible voltage: 250V AC, 30V DC. Permissible current: 2 A.

Cable: 4 x 0.93 mm2, Ø 6.6 ± 0.3 mm.

Characteristics of the input contacts:

Switched voltage: 5 V DC

Consumption: 10 mA.

Cable: 4 x 0.34 mm2, Ø 5 ± 0.5 mm.

UPS OFF

UPS ON

Communications Card Connection Example

If a SELV (safety extra low voltage) source is used, it must always be possible to isolate the communications card from the upstream source to ensure the safety of personnel working on the installation.

AC

communication card

Disconnecting device that can be locked

2 — 10

Setup and Installation

86-174010-00 B00

Page 32
Image 32
APC 40 130KVA user manual Characteristics of the input contacts, Communications Card Connection Example