3.5 Operation of Mimic-Panel LEDs
The MGE Galaxy 5000 system is simple to operate and yet provides a wealth of continuous monitoring and
diagnostic features to ensure proper operation. Operators gain access to information in the MGE Galaxy 5000
system through the display and its integrated LED mimic panel.
Figure 3-5: Operation of Mimic-Panel LEDs
Single UPS Start Sequence on Normal AC Input
Single UPS Start Sequence on Bypass AC Input
Steps Action LED (39) LED (40) LED (41) LED (42) LED (43)
1Q4S open Off Off Off Off Off
2Close Q4S Off Off red Off green
3Close Q5N Off Off red green green
4Open Q3BP Off Off red green green
5Close Q1 green Off red green green
6Close Battery CB green Off Off green green
7Press ON button (37) green green Off green Off
Steps Action LED (39) LED (40) LED (41) LED (42) LED (43)
1Q1 open Off Off Off Off Off
2Close Q1 green Off red Off red
3Close Battery CB green Off Off Off red
4Close Q4S green Off Off Off green
5Close Q5N green Off Off green green
6Open Q3BP green Off Off green green
7Press ON button (37) green green Off green Off
37
MGE Galaxy 5000
Operation3 — 4 86-174010-00 B00