MGE Galaxy 5000

3.5Operation of Mimic-Panel LEDs

The MGE Galaxy 5000 system is simple to operate and yet provides a wealth of continuous monitoring and diagnostic features to ensure proper operation. Operators gain access to information in the MGE Galaxy 5000 system through the display and its integrated LED mimic panel.

Figure 3-5: Operation of Mimic-Panel LEDs

37

Single UPS Start Sequence on Normal AC Input

 

Steps

Action

LED (39)

LED (40)

LED (41)

LED (42)

LED (43)

 

 

 

 

 

 

 

 

 

1

Q1 open

Off

Off

Off

Off

Off

 

 

 

 

 

 

 

 

 

2

Close Q1

green

Off

red

Off

red

 

 

 

 

 

 

 

 

 

3

Close Battery CB

green

Off

Off

Off

red

 

 

 

 

 

 

 

 

 

4

Close Q4S

green

Off

Off

Off

green

 

 

 

 

 

 

 

 

 

5

Close Q5N

green

Off

Off

green

green

 

 

 

 

 

 

 

 

 

6

Open Q3BP

green

Off

Off

green

green

 

 

 

 

 

 

 

 

 

7

Press ON button (37)

green

green

Off

green

Off

 

 

 

 

 

 

 

 

Single UPS Start Sequence on Bypass AC Input

 

 

 

 

 

 

 

 

 

 

 

 

 

Steps

Action

LED (39)

LED (40)

LED (41)

LED (42)

LED (43)

 

 

 

 

 

 

 

 

 

1

Q4S open

Off

Off

Off

Off

Off

 

 

 

 

 

 

 

 

 

2

Close Q4S

Off

Off

red

Off

green

 

 

 

 

 

 

 

 

 

3

Close Q5N

Off

Off

red

green

green

 

 

 

 

 

 

 

 

 

4

Open Q3BP

Off

Off

red

green

green

 

 

 

 

 

 

 

 

 

5

Close Q1

green

Off

red

green

green

 

 

 

 

 

 

 

 

 

6

Close Battery CB

green

Off

Off

green

green

 

 

 

 

 

 

 

 

 

7

Press ON button (37)

green

green

Off

green

Off

 

 

 

 

 

 

 

 

3 — 4

Operation

86-174010-00 B00

Page 38
Image 38
APC 40 130KVA user manual Operation of Mimic-Panel LEDs, Single UPS Start Sequence on Normal AC Input