BATTERY TEMPERATURE FAULT

Battery ambient temperature outside tolerances.

 

 

 

 

 

 

VENTILATION FAULT

Excessive temperature on one or more inductors OR

 

 

 

Inverter or AC bypass static switch fan fault.

 

 

 

 

 

 

EMERGENCY POWER OFF

EPO set on control-monitoring board OR

 

 

ACTIVATED

EPO set on charger board.

 

 

 

 

 

 

BATTERY CIRCUIT BREAKER(S)

One or two Battery circuit breaker is open.

 

 

OPEN

 

 

 

 

 

 

 

PHASE ROTATION FAULT

Phase inversion on normal AC input OR

 

 

 

Phase inversion on AC bypass.

 

 

 

 

 

 

FUSES BLOWN

Fuse blown at normal AC input OR

 

 

 

Charger fuse has blown OR

 

 

 

Power supply board fuse has blown OR

 

 

 

Inverter phase-1 fuse has blown OR

 

 

 

Inverter phase-2 fuse has blown OR

 

 

 

Inverter phase-3 fuse has blown.

 

 

 

 

 

 

TRANSFER TO BYPASS DISABLED

Transfer to AC bypass disabled (control and monitoring board checks

 

 

 

for disabling by the personalization and/or an SECI input).

 

 

 

 

 

 

ECO MODE ACTIVATED

The unit is operating in ECO mode. It is configured for ECO mode and

 

 

 

the static switch on the AC bypass is closed.

 

 

 

 

 

 

MAINTENANCE POSITION

Switch Q5N is open.

 

 

 

 

 

 

CHECK THE UPS

A Life Cycle Monitoring alarm has been activated:

 

 

 

End of warranty.

 

 

 

End of AC capacitor service life

 

 

 

End of DC capacitor service life

 

 

 

End of fan service lives.

 

 

 

End of power supply board service life.

 

 

 

End of battery service life.

 

 

 

 

 

Galaxy 5000 can be equipped with up to two SECI cards maximum. In this case, the second card must be identified differently. On the second card, microswitch 1 on SA1 must be set to ON.