General characteristics of Galaxy 5000 UPSs
INFORMATION The operating temperature range is 32°F to 104°F (0°C to +40°C); for overload
conditions is 32°F to 86°F (0°C to +30°C). Optimum operating range is within 68°F
to 77°F (20°C to +25°C). Battery backup time is adversely affected by high and low
temperatures. It is significantly reduced at temperatures under 50°F (10°C). Above
77°F (25°C), battery service life is cut in half every 18°F (10°C). Above 104°F (40°C),
battery manufacturers no longer guarantee operation due to the risk of thermal
runaway.
UPS power in KVA 40 50 60 80 100 130
Normal AC input
Number of conductors 3 phases + ground
Reference voltage at Pn 432 V to 528 V
Reference frequency 45 Hz to 65 Hz
THDI Typically 3% at Pn
Power factor >0.99
Bypass AC input
Number of conductors 3 phases + ground
Reference voltage at Pn 432 V to 528 V
Reference frequency 45 Hz to 65 Hz
Load output
Number of conductors 3 phases
Set phase-to-phase voltages 480 V
Voltage variation ± 1%
Adjustable frequencies and
tolerance (on battery power) 60 Hz ± 0.1 Hz
Voltage variation for 0 to
100% load step change ± 1%
Permissible overloads 150% for 1 minute, 125% for 10 minutes
THDU Ph-to-Ph and Ph-to-N
for nonlinear load < 2% Ph-to-Ph
Battery
Standard battery technology Sealed lead-acid battery (gas-recombination)
Inverter
Active power (kW) 36 45 54 72 90 11 7
Heat losses in kW Heat
Heat losses in BTUs
2.71
9250
3.39
11560
4.06
13870
5.42
18500
5.74
19610
7.47
25490
Storage temperature range -13°F to 103°F (-25°C to +45°C)
Relative humidity 20% to 95%
Maximum operating altitude
without derating 3281 ft (< 1000 m)
Operating temperature range
at Pn 32°F to 104°F (0°C to 40°C)