MGE Galaxy 5000

General characteristics of Galaxy 5000 UPSs

UPS power in KVA

40

50

60

80

100

130

 

 

 

 

 

 

 

 

 

 

Normal AC input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of conductors

3 phases + ground

 

 

 

 

 

 

 

 

 

 

 

 

 

Reference voltage at Pn

432 V to 528 V

 

 

 

 

 

 

 

 

 

 

 

 

 

Reference frequency

45 Hz to 65 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

THDI

Typically 3% at Pn

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

>0.99

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass AC input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of conductors

3 phases + ground

 

 

 

 

 

 

 

 

 

 

 

 

 

Reference voltage at Pn

432 V to 528 V

 

 

 

 

 

 

 

 

 

 

 

 

 

Reference frequency

45 Hz to 65 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of conductors

3 phases

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set phase-to-phase voltages

480 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage variation

± 1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjustable frequencies and

60 Hz ± 0.1 Hz

 

 

 

 

 

tolerance (on battery power)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage variation for 0 to

± 1%

 

 

 

 

 

 

100% load step change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permissible overloads

150% for 1 minute, 125% for 10 minutes

 

 

 

 

 

 

 

 

 

 

 

THDU Ph-to-Ph and Ph-to-N

< 2% Ph-to-Ph

 

 

 

 

 

for nonlinear load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard battery technology

Sealed lead-acid battery (gas-recombination)

 

 

 

 

 

 

 

 

 

 

 

 

Inverter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Active power (kW)

36

45

54

72

90

117

 

 

 

 

 

 

 

 

 

 

Heat losses in kW Heat

2.71

3.39

4.06

5.42

5.74

7.47

 

Heat losses in BTUs

9250

11560

13870

18500

19610

25490

 

 

 

 

 

 

 

 

 

 

Storage temperature range

-13°F to 103°F (-25°C to +45°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

Relative humidity

20% to 95%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum operating altitude

3281 ft (< 1000 m)

 

 

 

 

 

without derating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating temperature range

32°F to 104°F (0°C to 40°C)

 

 

 

 

at Pn

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INFORMATION The operating temperature range is 32°F to 104°F (0°C to +40°C); for overload conditions is 32°F to 86°F (0°C to +30°C). Optimum operating range is within 68°F to 77°F (20°C to +25°C). Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at temperatures under 50°F (10°C). Above 77°F (25°C), battery service life is cut in half every 18°F (10°C). Above 104°F (40°C), battery manufacturers no longer guarantee operation due to the risk of thermal runaway.

A — 4