APC 40 130KVA user manual Limitation

Models: 40 130KVA

1 76
Download 76 pages 38.78 Kb
Page 58
Image 58

MGE Galaxy 5000

When sizing the upstream circuit breakers, the parameters presented below must be taken into account: Time/current curves for UPS input and output fuses:

 

t (s)

 

 

104

 

 

 

103

 

 

 

102

 

 

 

10

 

 

40-80 kVA: 160A

 

 

 

1

 

 

100-130 kVA: 315A

10-1

 

 

 

10-2

 

 

 

10-3

 

 

 

10-4

 

 

I (A)

10

102

103

104

UPS short-circuit current with inverter coupled and By-pass AC source out of tolerances

 

Sn

 

40KVA

50KVA

 

60KVA

 

80KVA

 

100KVA

 

130KVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

In

 

 

48 A

60 A

 

72 A

 

96 A

 

120 A

 

156 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limitation

 

 

230 A

230 A

 

230 A

 

260 A

 

435 A

 

435 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Line Current Values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rated power of

 

Continuous input

Input current at

Input current at

 

Input/output fuse

 

each UPS unit

 

 

current at V=480V

V=480V overload

V=480V overload

 

ratings

 

 

 

 

 

 

 

 

= 1.25 In limited to

= 1.5 In limited to

 

 

 

 

 

 

 

 

 

 

10 min.

 

1 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40KVA

 

 

 

48 A

60 A

 

 

72 A

 

160 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50KVA

 

 

 

60 A

75 A

 

 

90 A

 

160 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60KVA

 

 

 

72 A

90 A

 

 

108 A

 

160 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80KVA

 

 

 

96 A

120 A

 

 

144 A

 

160 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100KVA

 

 

 

120 A

150 A

 

 

180 A

 

315 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

130KVA

 

 

 

156 A

195 A

 

 

234 A

 

315 A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A — 2

Appendices

86-174010-00 B00

Page 58
Image 58
APC 40 130KVA user manual Limitation