3.10.3List of Operating Status Conditions That May be Assigned to an SECI Output
Operating status | Description |
conditions |
|
|
|
GENERAL ALARM | PFC fault OR |
| Inverter fault OR |
| Bypass static switch fault OR |
| Charger fault OR |
| Thermal overload on AC bypass OR |
| Normal AC input fuse blown OR |
| ALIN board input fuse blown OR |
| Q3BP and Q5N are closed simultaneously OR |
| External Q3BP and external Q5N are closed simultaneously OR |
| EPO activated OR |
| Battery backup time ended, shift to wait mode OR |
| Battery temperature fault > 45°C , charger shutdown OR |
| Battery deep discharge OR |
| Charger shutdown due to battery room temperature outside tolerances OR |
| Abnormal presence of voltage on the output before closing the bypass static |
| switch. (frequency converter) OR |
| UPS in downgraded mode OR |
| External CAN communication fault OR |
| Internal CAN communication fault (GDEN, MIZNUS and CHAN) OR |
| CAN cable physically cut OR |
| CAN communication relay fault OR |
| UPS personalization fault. |
|
|
BATTERY FAULT | The battery will soon reach the end of its theoretical service life OR |
| Battery must be checked (following a faulty battery test) |
|
|
LOAD ON UPS | Inverter connected to the load and operating on normal AC input. |
| Battery operations due to a BPI or battery test are signalled as operation on the |
| normal AC input. |
|
|
LOAD ON AUTOMATIC | The static switch on the AC bypass is closed. |
BYPASS |
|
|
|
LOAD ON BATTERY | Inverter connected to the load and operating on battery power. |
POWER | Battery operations due to a battery test are not signalled. |
|
|
LOW BATTERY WARNING | Battery has reached the |
| thresholds may be user set. |
|
|
OVERLOAD | One of the unit modules (rectifier, inverter or AC bypass) is overloaded (thermal or |
| instantaneous). |
|
|
Operation | 3 — 9 |