MGE Galaxy 5000

PFC FAULT

Neutral leg fault OR

 

Neutral leg IGBT temperature outside tolerances OR

 

Voltage difference between 2 DC half-buses outside tolerances OR

 

Top DC half-bus voltage outside tolerances OR

 

Bottom DC half-bus voltage outside tolerances

 

PFC fault OR

 

DC-bus voltage at end of CSR1 walk-in is lower than a threshold OR

 

DC-bus voltage at end of DC walk-in is lower than a threshold OR

 

DC-bus voltage is higher than the high threshold OR

 

DC-bus voltage is lower than the minimum threshold

 

Mean DC-bus voltage is higher than the maximum setpoint OR

 

Mean DC-bus voltage is lower than the minimum setpoint OR

 

DC-bus voltage is higher than the fast hardware threshold OR

 

Temperature of the static switch on the AC normal outside tolerances OR

 

Temperature of the battery static switch outside tolerances OR

 

Rectifier is current limiting OR

 

Rectifier thermal overload OR

 

PFC IGBT base-plate temperature outside tolerances OR

 

IGBT inductor temperature outside tolerances.

 

 

INVERTER FAULT

Inverter short-circuit detected OR

 

Inverter current limiting OR

 

Inverter static switch failure OR

 

Temperature fault on inverter static switch OR

 

Inverter base-plate temperature outside tolerances OR

 

Inverter thermal overload OR

 

Inverter phase-1 fuse has blown OR

 

Inverter phase-2 fuse has blown OR

 

Inverter phase-3 fuse has blown OR

 

Inverter phase-1 voltage amplitude outside tolerances OR

 

Inverter phase-2 voltage amplitude outside tolerances OR

 

Inverter phase-3 voltage amplitude outside tolerances OR

 

Instantaneous inverter voltage outside tolerances OR

 

Inverter relay for parallel connection is faulty.

 

 

CHARGER FAULT

Fault of non-isolated supply on charger board OR

 

Fault of isolated supply on charger board OR

 

Opening fault on battery circuit breaker no. 1 OR

 

Opening fault on battery circuit breaker no. 2 OR

 

Charger IGBT temperature outside tolerances OR

 

Difference in charge-current measurements between safety and measurement

 

systems OR

 

Charge current on measurement system close to zero OR

 

Charge current on safety system close to zero OR

 

Charge current is higher than safety level OR

 

Difference in voltage measurements between safety and measurement systems

 

OR

 

Voltage on measurement system close to zero OR

 

Voltage on safety system close to zero OR

 

Battery voltage higher than safety level OR

 

Charger fuse blown.

 

 

AUTOMATIC-BYPASS

Supply fault for the static switch on the AC bypass OR

FAULT

Fault on static switch on AC bypass OR

 

Temperature of the static switch on the AC bypass outside tolerances.

 

 

BYPASS AC SOURCE OUT

Bypass AC source outside of tolerances (voltage and/or frequency).

OF TOLERANCE

 

 

 