Web/SNMP Management SmartSlot Card User’s Guide 38
Device Manager Menus
UPS Status Options continued
Output voltage,
continued
Silcon DP300E. Five status fields report the output values for a Silcon
DP300E series UPS.
Note: In the Control Console, use the Detailed UPS Information
option to access the Peak Output Current status.
Fault tolerance
(Symmetra Power
Array)
Two status fields report the Symmetra Power Array fault tolerance.
Note: In the Control Console, you use the Detailed UPS Information
option to access the fault tolerance status.
Continued on next page
Status Field Definition
Output Voltage How much AC voltage the UPS is providing to its attached
equipment for each phase.
Output Current How much current the output voltage is providing for each
phase.
Output Power The load placed on each phase by the attached equipment, in
total kVA.
Output Power
Percentage The load placed on each phase by the attached equipment,
expressed as a percentage of the of the kVA ava ilable from th e
UPS.
Peak Output
Current The highest current output by each phase.
Status Field Definition
Redundancy The number of power modules which can fail or be removed
without causing the Symmetra Power Array to generate a
Minimum Redundancy Lost event.
Present KVA
Capacity The maximum load that the Symmetra Power Array can
support.