Web/SNMP Management SmartSlot Card User’s Guide 43
Device Manager Menus
UPS Configuration Options
Overview The UPS menu’s Configuration option provides access to the
configurable parameters described in the following sections:
Utility line settings on this page
Alarm thresholds (Symmetra Power Array) on page 44
Shutdown parameters on page 45
General settings on page 46
Battery on page 39
Utility line settings The Utility Line settings and their values differ by UPS model.
Note: No Utility Line settings are available for a Silcon DP300E series
UPS.
Smart-UPS/Matrix-UPS. The following table describes the Smart-UPS
and Matrix-UPS Utility Line settings.
Continued on next page
Setting Definition
Output Voltage The nominal AC voltage level for the UPS output.
High Transfer
Volta ge The upper limit of acceptable input voltage. When the input
reaches this value, the UPS switches to battery operation
(Matrix-UPS) or starts using its SmartBoost feature
(Smart-UPS).
Low Transfer
Voltage
(Smart-UPS)
The lower limit of acceptable input voltage. When the input
reaches this value, a Smart-UPS starts using its SmartTrim
feature, or switches to battery operation, if it does not have
SmartTrim.
Note: For Matrix-UPS, this setting appears in the Control
Console’s Line Tr ansf er me nu, but the va lue cannot be
changed.
Vout Reporting
(Matrix-UPS)How Matrix-UPS scales its output voltage readings.
Sensitivity How sensitive the UPS is to distortions in the input voltage.
Note: Matrix-UPS always uses an Automatic setting.