Web/SNMP Management SmartSlot Card User’s Guide 64
Events Menu
Management Card and Device Events continued
UPS events,
continued
Continued on next page
Code Severity Description
0x020F Severe UPS: bypass not in range; either frequency or voltage.
0x0210 Informational UPS: bypass not in range cleared; either frequency or
voltage.
0x0211 Severe UPS: Bypass contactor stuck in bypass position.
0x0212 Informational UPS: Bypass contactor stuck in bypass position cleared.
0x0213 Severe UPS: Bypass contactor stuck in on-line position.
0x0214 Informational UPS: Bypass contactor stuck in on-line position cleared.
0x0215 Severe UPS: In bypass due to an internal fault.
0x0216 Informational UPS: In bypass due to an internal fault cleared.
0x0217 Severe UPS: In bypass due to an overload.
0x0218 Informational UPS: In bypass due to an overload cleared.
0x0219 Severe UPS: In maintenance bypass.
0x021A Informational UPS: In maintenance bypass cleared.
0x021B Severe UPS: Input circuit breaker tripped open.
0x021C Informational UPS: Input circuit breaker tripped open cleared.
0x021D Severe UPS: System level fan failure.
0x021E Informational UPS: System level fan failure cleared.
0x021F Severe UPS: Redundant Intelligence Module in control.
0x0220 Informational UPS: Redundant Intelligence Module in control cleared.
0x0221 Severe UPS: IIC inter-module communications failure.
0x0222 Informational UPS: IIC inter-module communications failure cleared.
0x0223 Severe UPS: No working Power Modules.
0x0224 Informational UPS: No working Power Modules cleared.
0x0225 Severe UPS: Load shutdown from bypass; input frequency or
voltage outside limits.
0x0226 Informational UPS: Load shutdown from bypass cleared; input frequency
or voltage outside limits.
0x0227 Severe UPS: Runtime below alarm threshold.
0x0228 Informational UPS: Runtime below alarm threshold cleared.
0x0229 Severe UPS: Extended Run Frame fault.
0x022A Informational UPS: Extended Run Frame fault cleared.
0x022B Severe UPS: Output voltage out of range.