Web/SNMP Management SmartSlot Card User’s Guide 63
Events Menu
Management Card and Device Events continued
UPS events,
continued
Continued on next page
Code Severity Description
0x0120 Severe UPS: Base module fan failure.
0x0121 Informational UPS: External battery pack communications established.
0x0122 Severe UPS: External battery pack communications lost.
0x0123 Informational UPS: Battery calibration test initiated.
0x0124 Informational UPS: Battery calibration complete.
0x0125 Informational UPS: Graceful shutdown initiated.
0x0126 Warning UPS: SmartBoost or SmartTrim relay failure.
0x0127 Informational UPS: SmartBoost or SmartTrim relay failure cleared.
0x0128 Warning UPS: Bad output voltage condition.
0x0129 Informational UPS: Bad output voltage condition cleared.
0x012A Warning UPS: Battery charger failure.
0x012B Informational UPS: Battery charger failure cleared.
0x012C Warning UPS: Internal battery temperature threshold violation.
0x012D Informational UPS: Internal battery temperature threshold violation
cleared.
0x012F Warning UPS: No batteries installed.
0x0130 Informational UPS: No batteries installed cleared.
0x0201 Severe UPS: Power Module failure.
0x0202 Informational UPS: Power Module failure cleared.
0x0203 Severe UPS: Intelligence Module failure.
0x0204 Informational UPS: Intelligence Module failure cleared.
0x0205 Severe UPS: Redundant Intelligence Module failure.
0x0206 Informational UPS: Redundant Intelligence Module failure cleared.
0x0207 Severe UPS: Battery failure.
0x0208 Informational UPS: Battery failure cleared.
0x0209 Severe UPS: Load(kVA) alarm threshold violation.
0x020A Informational UPS: Load(kVA) alarm threshold violation cleared.
0x020B Severe UPS: Redundancy lost.
0x020C Informational UPS: Redundancy returned.
0x020D Severe UPS: Redundancy below alarm threshold.
0x020E Informational UPS: Redundancy below alarm threshold cleared.