KVM Over the NET™ User Manual

Fan Location and Speed Information

Fan Location

The switch has 6 fans that feed realtime fan speed information to the WinClient / Java Client Device Management page.

6

5

4

3

2

1

The fan locations in the above image are listed in the Device Information section under Fan Speed. See , page 144, for details.

Fan Speed

The fan speed automatically adjusts according to temperature as follows:

ŠIf any sensor senses that the temperature is greater than 32° C, all the fans are set to spin at half speed.

ŠIf any sensor senses that the temperature is greater than 45° C, all the fans are set to spin at full speed.

ŠWhen all four sensors sense that the temperature is less than 40° C, all the fans return to half speed.

ŠWhen all four sensors sense that the temperature is less than 30° C, all the fans turn off.

224