Section 1
General Information

B-2 Appendix MN715

Table B-1 Parameter Block Values Level 1 Continued
Level 1 Blocks - Continued
Block Title Parameter P# Adjustable Range Factory User
Setting
INPUT OPERATING MODE 1401 0Keypad
1Standard Run
215 Speed
3Fan Pump 2Wire
4Fan Pump 3Wire
5Serial
6Process CTRL
73SPD ANA 2WIRE
83SPD ANA 3WIRE
9EPOT 2WIRE
10EPOT 3WIRE
Keypad
COMMAND SELECT 1402 0Potentiometer
10-10 VOLTS
20-5 VOLTS
34-20 mA
4EXB PULSE FOL
510V EXB
64-20 mA EXB
73-15 PSI EXB
8Tachometer EXB
9None
Potentio-
Meter
ANA CMD INVERSE 1403 0OFF, 1ON OFF
ANA CMD OFFSET 1404 -20.0 to +20.0%
(where ±0.5V=±20%) 0.0 %
ANA CMD GAIN 1405 80.0% to 120% 100.0%
CMD SEL FILTER 1406 0-6 3
PWR UP MODE OP 1407 1Primary Mode,
2Last, 3Local Primary
Mode
OUTPUT DIGITAL OUT #1 1501 0Ready
1Zero Speed Ready
DIGITAL OUT #2 1502 1Zero Speed
2At Speed
3At Set Speed Zero Speed
DIGITAL OUT #3
(Relay Out #1) 1503 3At Set Speed
4Overload
5Keypad Control
6Fault
At Speed
DIGITAL OUT #4
(Relay Out #2) 1504 7Drive On
8Reverse
9Process Error
Fault
ZERO SPD SET PT 1505 0 to MAX Speed 6.00Hz
AT SPEED BAND 1506 0-20Hz 2.00Hz
SET SPEED POINT 1507 0 to MAX Speed 60.00Hz