3-16 Receiving & Installation MN715
Size D2 Single Phase Power Installation
Jumper Configuration
Locate the Interface board, and place J100 on pins 2 & 3 for single phase operation.
Figure 3-11 Jumper Configuration
J100
Pins 1 & 2 = Three Phase
Pins 2 & 3 = Single Phase 1
2
3
J100
Figure 3-12 Size D2 Single Phase 230/460VAC Power Connections
L1 L2
L1 L2 L3
* Circuit
Breaker
Earth
See Recommended Tightening Torques in Section 6.
Note 3
Baldor
Series 15H
Control
*Optional
Line
Reactor
Note 1
Note 3
A1 B1
A2 B2
Note 4
Notes:
1. See Protective Devices described previously in this section.
2. Use same gauge wire for Earth ground as is used for L1, L2 and L3.
3. Metal conduit should be used. Connect conduits so the use of a
Reactor or RC Device does not interrupt EMI/RFI shielding.
4. See Line/Load Reactors described previously in this section.
Note 2
L1 L2
* Fuse
Connection
Note 1
*Optional components
not provided with control.
A1 B1
L1 Neutral
* Circuit
Breaker
*Line
Reactor
A1
A2
Single phase 2 wire ConnectionsSingle phase 3 wire Connections