Section 1
General Information

B-4 Appendix MN715

Table B-2 Parameter Block Values Level 2
Level 2 Blocks
Block Title Parameter P# Adjustable Range Factory User
Setting
OUTPUT LIMITS OPERATING ZONE 2001 0STD CONST TQ
1STD VAR TQ
2QUIET CONST TQ
3QUIET VAR TQ
STD
CONST TQ
MIN OUTPUT
FREQ 2002 0 to MAX Frequency 0.00Hz
MAX OUTPUT
FREQ 2003 0 to MAX Frequency 60.00Hz
PK CURRENT LIMIT 2004 1A to Peak Rated Current PK Control
Rating
PWM FREQUENCY 2005 1-5kHz (Standard)
1-15kHz (Quiet) 2500Hz
REGEN LIMIT 2020 0OFF, 1ON OFF
REGEN LIMIT ADJ 2021 0 - 500 0Hz
CUSTOM UNITS MAX DECIMAL PLACES 2101 0-5 0
VALUE AT SPEED 2102 1-65535/1-65535 0./
01000
VALUE DEC PLACES 2103 0-5 (Serial Only) 0
VALUE SPEED REF 2104 1 to 65535 (Serial Only) 00000/
01000
UNITS OF MEASURE 2105 See Table 4-2. -
UNITS OF MEASURE 2 2106 See Table 4-2. (Serial Only) -
PROTECTION EXTERNAL TRIP 2202 0OFF, 1ON OFF
LOCAL ENABLE INP 2205 0OFF, 1ON OFF
I2T Response 2206 0Fault, 1Current Limit then
Hold, 2 Current Limit then Retry Fault
I2T Trigger 2207 0.00% to 100.00% 10.00%
Peak CURR Timer 2208 0.000 to 65.655 seconds 0.000s
Foldback Gain 2209 0.01 to 10.00 1.00
MISCELLANEOUS RESTART AUTO/MAN 2301 0Manual, 1Automatic Manual
RESTART FAULT/HR 2302 0-10 0
RESTART DELAY 2303 0-120Seconds 0s
LANGUAGE SELECT 2304 0English, 1Espanol English
FACTORY SETTINGS 2305 0NO, 1STD Settings,
250Hz / 400Volts NO
STAB CUTOFF FREQ 2320 0-4.00Hz 0.00Hz
STABILITY GAIN 2321 1-6 1
SECURITY
CONTROL SECURITY STATE 2401 0Off
1Local Security
2Serial Security
3Total Security
OFF
ACCESS TIMEOUT 2402 0-600seconds 0s
ACCESS CODE 2403 0-9999 9999