Section 1
General Information
4-6 Programming & Operation MN715
Initialize New Software EEPROM
After a new EEPROM is installed, the control will automatically initialize the new software
version and memory locations as if STD Settings was selected. If you need to initialize
the control to the 50Hz / 400Volts settings, use the following procedure.
Note: All parameter values already programmed will be changed when resetting the
control to factory settings.
Action Description Display Comments
Apply Power Keypad Display shows this
opening message. Logo display for 5 seconds.
If no faults and programmed for
LOCAL operation. Display mode. Stop LED on.
Press PROG key Enter program mode.
Press or key Scroll to Level 2 Blocks.
Press ENTER key Select Level 2 Blocks.
Press or key Scroll to the Miscellaneous block.
Press ENTER key Select Miscellaneous block.
Press key Scroll to Factory Settings
parameter.
Press ENTER key Access Factory Settings
parameter. represents blinking cursor.
Press key Scroll to STD SETTINGS, to
choose original factory settings. For 50Hz motors, set to
50Hz/400 VOLTS.
Press ENTER key Restores factory settings. Loading Presets is first message
Operation Done is next
No is displayed last.
Press key Scroll to menu exit.
Press ENTER key Return to display mode. Display mode. Stop LED on.
Press DISP key Scroll to diagnostic info block. If you wish to verify the software
version, enter diagnostic info.
Press ENTER key Access diagnostic information. Displays commanded speed,
direction of rotation, Local/
Remote and motor speed.
Press DISP key Display mode showing software
version and revision installed in
the control.
Verify new software version.
Press DISP key Displays exit choice. Press ENTER to exit diagnostic
information.