Section 1
General Information

Receiving & Installation 3-33MN715

Electronic Pot 3 Wire Operating Mode

Provides speed Increase and Decrease inputs to allow EPOT operation with 3 wire

inputs. The opto inputs can be switches as shown in Figure 3-33 or logic signals from

another device.

Figure 3-33 EPOT, 3 Wire Control Connection Diagram
See recommended terminal
tightening torques in Section 6.
J4-8 CLOSED allows normal control operation.
OPEN disables the control and motor coasts to a stop.
J4-9 Momentary CLOSED starts motor operation in the Forward direction.
J4-10 Momentary CLOSED starts motor operation in the Reverse direction.
Note: Closing both J4-9 and J4-10 at the same time will reset a fault condition.
J4-11 Momentary OPEN motor decels to stop (depending on Keypad Stop mode).
J4-12 CLOSED selects the Level 1, Input, Command Select parameter value.
OPEN selects EPOT.
J4-13 CLOSED selects ACC / DEC / S-CURVE group 2.
OPEN selects ACC / DEC / S-CURVE group 1.
J4-14 Momentary CLOSED increases motor speed while contact is closed.
J4-15 Momentary CLOSED decreases motor speed while contact is closed.
J4-16 If J4-16 is connected, you must set Level 2 Protection block, External Trip to
ON to activate the opto input.
CLOSED allows normal control operation.
OPEN causes an external trip fault. The control will disable and the motor
coasts to a stop. An external trip fault is displayed (also logged in the fault log).
8
9
10
11
12
13
14
15
16
17
Enable
Forward Run
Reverse Run
Stop
EPOT/Command Select
Accel/Decel Rate Select
External Trip
Opto In Common
Analog GND
Analog Input 1
Pot Reference
Analog Input +2
Analog Input -2
Analog Out 1
Analog Out 2
1
2
3
4
5
6
7
Increase
Decrease
Refer to Figure 3-35.
5KW
J4