Fan Pump 3 Wire Operating Mode

Operation in the Fan Pump 3-Wire mode is controlled by the opto isolated inputs at J4-8 through J4-16. The opto inputs can be switches as shown in Figure 3-29 or logic signals from another device.

Figure 3-29 Fan Pump, 3 Wire Control Connection Diagram

J4-8

CLOSED allows normal control operation.

 

 

 

 

 

 

 

 

 

Analog GND

 

OPEN disables the control and the motor coasts to a stop.

Command Pot or

 

J4-9

MOMENTARY CLOSED starts motor operation in the Forward direction.

 

Analog Input 1

Note:

Closing both J4-9 and J4-10 at the same time will reset a fault condition.

 

0-10VDC

 

Pot Reference

 

 

 

 

 

 

 

5KW

 

 

 

 

 

 

 

 

Analog Input +2

J4-10

MOMENTARY CLOSED starts motor operation in the Reverse direction.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Input -2

Note:

Closing both J4-9 and J4-10 at the same time will reset a fault condition.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Out 1

J4-11

OPEN motor decels to stop (depending on Keypad Stop mode).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Analog Out 2

J4-12

CLOSED selects STOP/START and Reset commands from terminal strip.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enable

 

OPEN selects STOP/START and Reset commands from Keypad.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Forward Run

J4-13

CLOSED allows other selections, see Speed Select Table 3-11.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reverse Run

 

OPEN selects speed commanded from Keypad (if J4-14 and J4-15 are closed).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop

J4-14

Firestat. Selects Level 1, Preset Speeds, Preset Speed #1.

 

 

 

 

 

 

 

 

 

J4-15

Freezestat. Selects Level 1, Preset Speeds, Preset Speed #2 (if J4-14 is closed).

 

 

 

Run Command

 

Speed Command

J4-16

If J4-16 is connected, you must set Level 2 Protection block, External Trip to “ON”

 

 

 

Firestat

 

to activate the opto input.

 

 

 

 

 

 

 

 

 

 

CLOSED allows normal control operation.

 

 

 

 

 

 

 

 

 

Freezestat

 

OPEN causes an external trip fault. The control will disable and the motor coasts

 

 

 

External Trip

 

to a stop. An external trip fault is displayed (also logged in the fault log).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Opto In Common

J4

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

Refer to Figure 3-35.

See recommended terminal tightening torques in Section 6.

Table 3-11 Speed Select Table – Fan Pump, 3 Wire

J4-13

J4-14

J4-15

Command

 

Open

 

Level 1, Preset Speeds, Preset Speed #1

 

Closed

Open

Level 1, Preset Speeds, Preset Speed #2

Open

Closed

Closed

Keypad Speed Command

Closed

Closed

Closed

Analog Input (Level 1, Input, Command Select)

MN715

Receiving & Installation 3-29

Page 40
Image 40
Baldor 15H manual Fan Pump 3 Wire Operating Mode, Speed Select Table Fan Pump, 3 Wire, J4-13 J4-14 J4-15 Command

Inverter Control, 15H specifications

The Baldor 15H Inverter Control stands out as a leading solution in the realm of variable frequency drives (VFDs), specifically designed for enhancing motor efficiency and performance in industrial applications. This control unit is engineered to provide robust and reliable performance while ensuring seamless integration with various motor types.

One of the main features of the Baldor 15H is its advanced control algorithms, which facilitate precise motor control. This technology allows for smooth acceleration and deceleration, reducing mechanical stress on the system and extending the lifespan of both the motor and connected equipment. The inverter control is adept at handling both synchronous and asynchronous motors, making it highly versatile for different operational needs.

The Baldor 15H incorporates a user-friendly interface that provides operators with real-time data and diagnostics. This feature allows for easy monitoring and troubleshooting, helping to minimize downtime and maintenance costs. The intuitive control panel simplifies parameter adjustments, enabling quick customization for specific application requirements.

Safety is paramount in industrial environments, and the Baldor 15H includes several safety features designed to protect both the equipment and personnel. These features include overload protection, overvoltage protection, and short-circuit protection, ensuring reliable operation even under demanding conditions.

Energy efficiency is another critical aspect of the Baldor 15H. By utilizing pulse-width modulation (PWM) technology, it optimizes power usage, which translates to lower energy costs and reduced environmental impact. This makes it an excellent choice for companies aiming to improve their sustainability practices.

Moreover, the Baldor 15H supports a variety of communication protocols, allowing for easy integration into existing automation systems. This capability ensures that operators can utilize the inverter control within modern industrial networks, enhancing overall system efficiency.

In terms of physical characteristics, the Baldor 15H is designed for durability and reliability. It comes with a robust enclosure that protects against dust, moisture, and other environmental factors commonly found in industrial settings. Its compact design also allows for easy installation in limited spaces.

Overall, the Baldor 15H Inverter Control is a comprehensive solution that combines advanced technology, safety features, and energy efficiency, making it a preferred choice for industries looking to optimize their motor control systems. Its adaptability to different motor types and integration capabilities further solidify its position as a leader in VFD technology.