Section 1
General Information

3-30 Receiving & Installation MN715

3 Speed Analog 2 Wire Operating Mode

Allows selection of 3 preset speeds with 2 wire inputs. The opto inputs can be switches as

shown in Figure 3-30 or logic signals from another device. Preset speeds are set in the Level

1 Preset Speeds block, Preset Speed #1, Preset Speed #2 and Preset Speed #3.

Figure 3-30 3 Speed Analog, 2 Wire Control Connection Diagram
See recommended terminal
tightening torques in Section 6.
8
9
10
11
12
13
14
15
16
17
Enable
Forward Run
Reverse Run
Analog Input Select
Run Command
Speed Command
External Trip
Opto In Common
Analog GND
Analog Input 1
Pot Reference
Analog Input +2
Analog Input -2
Analog Out 1
Analog Out 2
1
2
3
4
5
6
7
Switch 1
Switch 2
J4
Refer to Figure 3-35.
J4-8 CLOSED allows normal control operation.
OPEN disables the control and the motor coasts to a stop.
J4-9 CLOSED operates the motor in the Forward direction (with J4-10 open).
OPEN motor decels to stop (depending on Keypad Stop mode).
J4-10 CLOSED operates the motor in the Reverse direction (with J4-9 open).
OPEN motor decels to stop (depending on Keypad Stop mode).
Note: Closing both J4-9 and J4-10 at the same time will reset a fault condition.
J4-11 CLOSED selects Analog Input #1.
OPEN selects Level 1 Input block, Command Select parameter.
J4-12 CLOSED selects STOP/START and Reset commands from terminal strip.
OPEN selects STOP/START and Reset commands from Keypad.
J4-13 CLOSED selects Level 1 Input block, Command Select parameter.
OPEN selects speed commanded from the keypad.
Note: When changing from Terminal Strip to Keypad (J4-12 or J4-13) the motor speed
and direction will remain the same after the change.
J4-14 Selects speed command as defined in the Speed Select Table 3-12.
J4-15 Selects speed command as defined in the Speed Select Table 3-12.
J4-16 If J4-16 is connected, you must set Level 2 Protection block, External Trip to ON
to activate the opto input.
CLOSED allows normal control operation.
OPEN causes an external trip fault. The control will disable and the motor coasts
to a stop. An external trip fault is displayed (also logged in the fault log).
5KW
Command Pot or
0-10VDC
Table 3-12 Speed Select Table 3 Speed Analog, 2 Wire
J4-14 J4-15 Command
Open Open Analog Input (Level 1, Input, Command Select)
Closed Open Level 1, Preset Speeds, Preset Speed #1
Open Closed Level 1, Preset Speeds, Preset Speed #2
Closed Closed Level 1, Preset Speeds, Preset Speed #3