Bosch Appliances D6600 9.4.1, Minimum Standby Battery, Device, V Battery Standby, Current, 4 hr

Models: D6600

1 88
Download 88 pages 54.03 Kb
Page 28
Image 28
Device

28 en Power

Conettix Communications Receiver/

Gateway

 

 

 

11.5 V to 10.2 V

Battery Low

 

 

 

 

 

 

 

 

 

 

 

Below 10.2 V

Battery Bad

 

 

Battery Missing

 

 

 

 

 

 

 

 

Table 9.1: Battery Voltage Display

 

 

 

 

 

 

 

 

 

 

 

 

 

Device

 

Qty

12 V Battery Standby

UPS AC Standby Current

 

 

 

Current

 

 

 

 

 

 

 

 

 

 

 

D6600

(one D6640/ D6641/

1

800 mA

800 m

350 mA

350 mA

D6645

Card)

 

 

A

 

 

 

 

 

 

 

 

 

Additional D6640/ D6641/

 

210 mA x Qty (2

 

35 mA x Qty (2

 

D6645

Cards

 

to 7)

 

to 7)

 

 

 

 

 

 

 

Additional D6650/D6655

 

300 mA x Qty (1

 

50 mA x Qty (1

 

Cards

 

 

to 8)

 

to 8)

 

 

 

 

 

 

 

 

D6672

COM1 Adapter

 

10 mA (if

 

2 mA (if

 

 

 

 

installed)

 

installed)

 

 

 

 

 

 

 

Total Standby Current:

 

 

 

Total UPS

 

 

 

 

 

 

Current:

 

 

 

 

 

 

Table 9.2: Calculating Standby Current for the D6600

 

 

 

 

The standby current required for the D6600 depends on the number of optional cards installed in the receiver. Use the table above to calculate the D6600 standby current. The standby current required by the D6100IPv6 is listed in the table below.

 

 

12 V Battery Standby

 

UPS AC Standby Current

 

 

 

 

 

 

 

 

 

 

330 mA

 

250 mA

 

 

 

 

 

 

 

 

 

 

Table 9.3: Standby Current for the D6100IPv6

 

 

 

 

 

 

 

 

 

 

 

i

Notice!

 

 

 

 

 

18 Ah batteries are required to meet 24-hour standby requirements.

 

 

 

 

 

 

 

 

 

 

 

9.4.1

 

Minimum Standby Battery

 

 

 

 

 

The table below shows the maximum standby current for common rechargeable battery

 

 

capacities at 4-hour, 8-hour, and 24-hour standby periods. If the standby current is larger than

 

 

the value listed, you must use the next larger capacity battery.

 

 

 

 

 

 

 

 

 

Rechargeable Battery

Maximum Standby Current (mA)

 

 

 

Capacity

 

 

 

 

 

 

4 hr

 

8 hr

24 hr

 

 

 

 

 

 

 

 

 

 

 

 

 

7 Ah

1400

 

700

230

 

 

 

 

 

 

 

 

 

8 Ah

1600

 

800

265

 

 

 

 

 

 

 

 

 

18 Ah

3600

 

1800

600

 

 

 

 

 

 

 

 

 

Includes 20% battery de-rating storage factor

 

 

 

 

 

 

 

 

 

 

2012.11 08 4998122704