Clear Pending Events (Function 4)

38 en D6600/D6100IPv6 Operation

Conettix Communications Receiver/

Gateway

 

 

 

Clear Pending Events (Function 4)

Use this option to clear all pending events.

Running the Clear Pending Events function:

1.Press the Function key. Enter your password and press the Enter key to go to the Welcome Manager.

2.Press [4] and Enter.

3.Press [0] to cancel the function and not delete all pending events, or press [1] to clear all pending events.

LCD/LED Availability Test (Function 5)

Use this option to clear all pending events.

Running the LCD/LED Availability Test function:

1.Press the Function key. Enter your password and press the Enter key to go to the Welcome Manager.

2.Press [6] and Enter.

The LCD changes all segments to black for 2 sec so that you can check for nonfunctioning LCD segments. All D6641 Line Cards turn the line LEDs on red for 2 sec and then green for 2 sec. The Power and System trouble LEDs turn on for 2 sec, then off. After the test completes, the system restores the LEDs to their previous state.

11.5 Busy Seconds (Line Busy) Reports

 

The D6600/D6100IPv6 monitors and reports when a call group of receiver lines cannot receive

 

signals. The receiver cannot process signals if its incoming telephone lines are in trouble, if

 

other communicators have the line tied up, or if the line card is inoperative. The receiver

 

interprets telephone lines that are not in trouble and taking calls as busy time. Telephone lines

 

that are in trouble are not included in the busy time calculation.

 

The amount of busy time accumulated during a 10 min period is the basis for a Busy Seconds

 

Reports. The 10 min busy period begins when all lines in a call group become busy, or when a

 

non-programmed single line for a call group becomes busy. The D6600/D6100IPv6 totals the

 

accumulated busy time and prints the Busy Seconds Report after the 10 min period ends.

 

After at least 60 sec (10%) of busy time, the receiver generates a report. The D6600/

 

D6100IPv6 reports up to 100% busy time.

 

Program the Busy Seconds Reports option to No if Busy Seconds Reports are not wanted for

 

all lines. Setting the Line Sniff option to 2 disables reports for individual lines.

 

 

i

Notice!

Enable Seconds Reports for UL Listed central stations.

 

 

 

 

UL inspectors might investigate the amount of time the digital receiver lines cannot receive

 

signals. Ensure that lines are available to process emergency signals on a timely basis.

 

Excessive Line Busy Reports can indicate it is necessary to install additional lines in rotary

 

with your primary receiver lines.

 

Assign each line to a call group. For the group to start accumulating busy time, all lines in the

 

call group must be online, in trouble, or without an operating line card.

2012.11 08 4998122704