Bosch Appliances D6600 Ports, Radionics D6615 CPU Terminator Card, Bosch D6615 CPU Terminator C

Models: D6600

1 88
Download 88 pages 54.03 Kb
Page 32
Image 32
Ports

32 en Input and Output Ports

Conettix Communications Receiver/

Gateway

 

 

 

 

 

Warning!

!Operating the input as an analog input between 0.5 V and 5 V might cause abnormal results. This input state is not defined and might change expected results.

i

Notice!

Reverse configuration is not for use in UL Listed applications.

 

10.1.2Automation Link Monitoring (COM3) through CPU Programmable Output

Ports

The output connections on the I/O port have an open collector transistor output that can activate an external sounder or light if the automation system fails.

i

Notice!

 

Configure external devices using the specifications listed in the table below. Outputs are not

 

verified by UL.

 

 

 

 

 

 

 

 

Radionics D6615 CPU Terminator Card

Bosch D6615 CPU Terminator C

 

 

 

 

Solid state output provides a current sink to

Solid State output provides a current sink to

 

common (-)

common (-)

 

 

 

 

Maximum load is 20 mA

Maximum load is 75 mA

 

 

 

 

Vsat @ 1 mA = 0.5 VDC

Vsat @ 10 mA = 0.5 VDC

 

 

 

 

Vsat @ 10 mA = 3.0 VDC

Vsat @ 25 mA = 1.0 VDC

 

 

 

 

Maximum voltage = 30 VDC

Vsat @ 50 mA = 2.5 VDC

 

 

 

 

 

Maximum voltage = 30 VDC

 

 

 

 

Table 10.1: Terminator Card Configuration

 